| Plan Review Notes For Permit 13080472 |
| Permit Number |
13080472 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-16 18:59:49 | RESIDENTIAL (R3) REPAIR/RENOVATION MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE EQUIPMENT SIZING CALCULATIONS. EQUIPMENT TO | | | MATCH EQUIPMENT LISTED ON A/C PLANS. | | | ***NOTE; SPECIFY ON A/C PLANS ALL EQUIPMENT SHOWN ON | | | THE SIZING CALCULATIONS. | | | | | | 2- MASTER BATHROOM NEEDS ANOTHER EXHAUST FAN AS | | | REQUIRED BY SEC. M1507.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 3- MASTER BEDROOM TRANSFER GRILL DOESN'T COMPLY WITH | | | SEC. M1602.4. REVISE SIZE AS REQUIRED. NEED 50SQUARE | | | INCHES FOR EACH 100CFM SUPPLIED. AND MASTER BEDROOM | | | NEED TO SIZE TRANSFER GRILL ACCORDING TO ALL THE AIR | | | THAT IS SUPPLIED INTO THE MASTER SUITE. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|