| 2013-08-16 17:35:55 | RESIDENTIAL (R3) REPAIRS/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. PROVIDE ONLY THE PRODUCT APPROVAL COVER PAGE AND |
| | PAGE SHOWING THE SPECIFIED CONNECTOR. |
| | |
| | B) GARAGE DOOR. NOA 10-0216.03 SUBMITTED WAS SUPERSEDED |
| | BY MIAMI-DADE. PROVIDE CURRENT NOA. |
| | |
| | C) INSWING ENTRY DOOR AS SHOWN ON PLANS. (AND CLARIFY |
| | WHERE IS THE ALUMINUM/GLASS DOOR WITH NOA 12-0208.14 |
| | SUBMITTED GOING TO BE INSTALLED?. IS THIS FOR THE |
| | GARAGE SIDE DOOR? |
| | |
| | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS. |
| | |
| | 3- SPECIFY TRUSS CONNECTOR AT BOTH ENDS. ONLY CONNECTOR |
| | TO THE EXISTING CONCRETE BLOCK WALL WAS SPECIFIED ON |
| | SHEET A-5-0. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 4- PROVIDE ENERGY CALCULATIONS. SEC. 101.4.3 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 5- SHEET A-5-1; CLEARLY SPECIFY ROOF SHEATHING FOR ALL |
| | ROOF ZONES, INCLUDING ROOF ZONE 3. SEC. R803.2.3.1 OF |
| | 2010 FBC-RESIDENTIAL REQUIRES 8D RING SHANK NAILS AT 4" |
| | O.C. IN ZONE 3. NAILING SCHEDULE DOESN'T SPECIFY THE |
| | ROOF ZONE 3. AND, SEE FIGURE R803.2.3.1 FOR AL ROOF |
| | ZONES MINIMUM DIMENSIONS. REVISE THE ROOF SHEATHING |
| | DETAIL, ROOF COVERING DETAIL AND NAILING SCHEDULE AS |
| | REQUIRED. |
| | |
| | 6- ARCHITECT'S TITLE BLOCK TO PROVIDE A SPACE FOR THE |
| | PRINTED NAME AND LICENSE NUMBER OF THE PERSON SEALING |
| | THE DOCUMENT AS REQUIRED BY CHAPTER 481 AND SEC. |
| | 61G1-16.004 OF FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 7- SHEET A-2.2: REVISE THE SPECIFICATIONS FOR THE |
| | GARAGE DOOR THAT LEADS TO THE LAUNDRY. DOOR NEEDS TO |
| | COMPLY WITH SEC. R302.5.1 OF 2010 FBC-RESIDENTIAL. |
| | |