| Plan Review Notes For Permit 13080460 |
| Permit Number |
13080460 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-10-19 11:26:58 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6724 | | | | | | FROM PREVIOUS LISTS: | | | | | | 1. INSTALLATION SCHEDULE IS INCOMPLETE. SHUTTER | | | MOUNTING CONNECTION TYPE, ANCHOR SPACING, SUBSTRATE NOT | | | COMPLETED | | | | | | 2ND REVIEW, THIS INFORMATION NOT PROVIDED. SHUTTER | | | MOUNTING CONNECTION TYPE SHOULD CORRELATE WITH THE | | | ANCHOR CHARTS (SEE SHEET 11) FOR EXAMPLE, 1 (TOP) OR 5 | | | (BOTTOM). | | | | | | SUBSTRATE SHOULD BE THE SUBSTRATE FOR THE OPENING. THIS | | | IS TYPICALLY CONCRETE ON THE TOP, BLOCK ON THE BOTTOM | | | DUE TO EDGE DISTANCE REQUIREMENTS. | | | | | | ANCHOR SPACING - SELF EXPLANATORY. THIS COLUMN IS | | | REQUIRED. | | | | | | 2-3. OK | | | | | | |
|