| Plan Review Notes For Permit 13080442 |
| Permit Number |
13080442 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-14 10:46:57 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) THIS STRUCTURE IS LOCATED IN A 170 MPH VULT / 132 | | | MPH VASD WIND SPEED AND THE EXPOSURE CATEGORY IS D. THE | | | REQUIRED UPLIFT FOR A ROOF SLOPE OF 0 TO 7 DEGREES WITH | | | A 20 FT MEAN ROOF HEIGHT IS -82 PSF IN ROOF ZONE 2 AND | | | -123 PSF IN ROOF ZONE 3. THE MAXIMUM DESIGN PRESSURE IS | | | -60.0 PSF FOR THE SEALOFLEX W-5 SYSTEM THAT WAS | | | SPECIFIED. THIS DESIGN PRESSURE DOES NOT MEET THE | | | REQUIRED PRESSURES FOR ZONES 2 AND 3. ACCORDING TO THE | | | PRODUCT APPROVAL NOTE #8 THE MAXIMUM DESIGN PRESSURE | | | FOR FULLY BONDED ASSEMBLIES CAN NOT BE INCREASED BY | | | RATIONAL ANALYSIS. PLEASE SUBMIT PRODUCT APPROVALS FOR | | | A COMPLIANT ASSEMBLY. DCA RULE 9N-3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|