Plan Review Notes
Plan Review Notes For Permit 13080440
Permit Number 13080440
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-21 12:57:15BUILDING PLAN REVIEW
 PERMIT: 13080440
 ADD: 301 53RD ST UNIT A
 CONT: BESA CONSTRUCTION
 TEL: (561)605-3399
  
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: AUGUST 21/ 2013
 ACTION: DENIED
  
 1) CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE
 FLORIDA BUILDING CODE 2010 CHAPTER 1 ADMINISTRATION
 107.1 WHO EVER THE DESIGNER IS FOR THE BUILDING SET OF
 PLANS WILL NEED TO PRINT, SIGN THEIR NAME AND LICENSE
 NUMBER ON THE PLANS, FOR EACH OF THE TRADES. THE CGC
 CAN ONLY DESIGN THE BUILDING PORTTION OF PLANS, AND
 THEY HAVE TO ALSO BE THE ONES TO COMPLETE THE WORK
 UNDER THE PERMIT, THIS GOES FOR EACH OF THE TRADES
 INVOLED.
  
 2) THE PLANS DO NOT PROVIDE WHAT THE UNIT LOOKED LIKE
 BEFORE THE REMODEL, WE ARE UNABLE TO KNOW WHAT IS
 EXISTING AND WHAT IS NEW. PLEASE PROVIDE EXISTING AND
 PROPOSED FLOOR PLANS. CITY OF WEST PALM BEACH LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE 2010 CHAPTER 1
 ADMINISTRATION 107.2.1 CONSTRUCTION DOCUMENTS SHALL BE
 OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE
 AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT
 IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL. SUCH DRAWINGS AND
 SPECIFICATIONS SHALL CONTAIN INFORMATION, IN THE FORM
 OF NOTES OR OTHERWISE, AS TO THE QUALITY OF MATERIALS,
 WHERE QUALITY IS ESSENTIAL TO CONFORMITY WITH THE
 TECHNICAL CODES.
  
 3) PLEASE IDENTIFY IF THIS UNIT IS A TOWNHOUSE UNIT OR
 IS THIS A TOWNHOUSE UNIT, IT WILL DETERMINE TO WHICH
 CODE BOOK WE CONDUCT OUR REVIEW.
 CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2010 CHAPTER 1 ADMINISTRATION 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIED.
  
 4) THE PLANS INDICATE WHAT APPEARS TO BE A DOOR OPENING
 TO THE EXTERIOR FROM THE RENOVATED BATHROOM, IS THIS A
 NEW OPENING, IF SO PLEASE PROVIDE THE TYPE OF EXTERIOR
 WALLS ARE BEING CONSTRUCTEDPROVIDE FINSHES AND PRODUCT
 APPROVALS FOR THE NEW DOOR OPENING. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) PLANS APPEAR THAT PARTS OF THE BATHROOM FLOOR WILL
 BE REMOVED FOR THE NEW PLUMBING WASTE PIPING. PLEASE
 PROVIDE HOW THE FLOOR SLAB IS GOING TO BE REPAIRED IF
 IT IS A CONCRETE SLAB. 107.2.1.3 ADDITIONAL INFORMATION
 IS REQUIRED. PLEASE PROVIDE DETAILS FOR COMPLIANCE
 WITH:
 5A) 2010 FBC 1816.1.4
 IF SOIL TREATMENT IS USED FOR SUBTERRANEAN TERMITE
 PREVENTION, CHEMICALLY TREATED SOIL SHALL BE PROTECTED
 WITH A MINIMUM 6 MILLIMETER VAPOR RETARDER TO PROTECT
 AGAINST RAINFALL DILUTION. IF RAINFALL OCCURS BEFORE
 VAPOR RETARDER PLACEMENT, RETREATMENT IS REQUIRED. ANY
 WORK, INCLUDING PLACEMENT OF REINFORCING STEEL, DONE
 AFTER CHEMICAL TREATMENT UNTIL THE CONCRETE FLOOR IS
 POURED, SHALL BE DONE IN SUCH MANNER AS TO AVOID
 PENETRATING OR DISTURBING TREATED SOIL.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]