| Plan Review Notes For Permit 13080433 |
| Permit Number |
13080433 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-15 18:11:37 | 2010 FBC | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF A FLOOR PLAN/ ROOF FRAMING PLAN | | | SHOWING THE LOCATION OF THE POST AND BEAM DETAIL THAT | | | WAS SUBMITTED. SPECIFY THE SPAN OF THE BEAM ON THE | | | DETAIL. CITY AMENDMENTS 107.2.1 | | | | | | 2) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE PRECAST | | | 12" X 12" X 8" CONCRETE PAD AND SPECIFY THE SIZE OF THE | | | STEEL REINFORCING BARS. DCA RULE 9N-3 | | | | | | 3) SHOW COMPLIANCE WITH FBCR 317.1 FOR FOR PROTECTION | | | OF WOOD FROM DECAY WHEN CLOSER THAN 18" TO THE EXPOSED | | | GROUND. | | | | | | 4) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE | | | SIMPSON CONNECTORS AS REQUIRED BY DCA RULE 9N-3. | | | | | | 5) PLEASE CLARIFY IF THE 3 - 2 X 4 COLUMN IS REQUIRED | | | TO BE NAILED TOGETHER AND SPECIFY THE FASTENERS AND | | | SPACING. CITY AMENDMENTS 107.2.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|