| Plan Review Notes For Permit 13080425 |
| Permit Number |
13080425 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-21 19:30:41 | RESIDENTIAL (R30 ALTERATION/RENOVATION MECHANICAL | | | REVIEW COMMENTS. | | | CODE ; 2010 FBC. | | | | | | 1- RETURN AIR CAN'T BE LOCATED BY THE KITCHEN. SEC. | | | M1602.2 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- PROVIDE COMPLETE REPORT OF THE EQUIPMENT SIZING | | | CALCULATIONS. ONLY ONE PAGE WAS SUBMITTED. AND, PROVIDE | | | THE HEATIING CALCULATIONS. SEC. 403.6 OF 2010 | | | FBC-ENERGY CONSERVATION. | | | | | | 3- INFORMATION SHOWN ON THE ENERGY CALCULATIONS DOESN'T | | | MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING | | | CALCULATIONS. SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | 4- THERE ARE TWO A/C PLANS SUBMITTED WITH DIFFERENT | | | INFORMATION. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1 | | | CITY AMENDMENTS. | | | | | | 5- PERSON RESPONSIBLE FOR THE DESIGN OF THE A/C PLAN TO | | | PROVIDE NAME AND SIGNATURE. SEC. 107.2.1 CITY | | | AMENDMENTS. | | | | | | 6- SIZE OF TRANSFER DUCT FOR BEDROOM #3 DOESN'T COMPLY | | | WITH EXCEPTION #3 OF SECTION M1602.4 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|