2013-08-21 19:30:41RESIDENTIAL (R30 ALTERATION/RENOVATION MECHANICAL
 REVIEW COMMENTS.
 CODE ; 2010 FBC.
  
 1- RETURN AIR CAN'T BE LOCATED BY THE KITCHEN. SEC.
 M1602.2 OF 2010 FBC-RESIDENTIAL.
  
 2- PROVIDE COMPLETE REPORT OF THE EQUIPMENT SIZING
 CALCULATIONS. ONLY ONE PAGE WAS SUBMITTED. AND, PROVIDE
 THE HEATIING CALCULATIONS. SEC. 403.6 OF 2010
 FBC-ENERGY CONSERVATION.
  
 3- INFORMATION SHOWN ON THE ENERGY CALCULATIONS DOESN'T
 MATCH INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4- THERE ARE TWO A/C PLANS SUBMITTED WITH DIFFERENT
 INFORMATION. REVISE AS REQUIRED TO MATCH. SEC. 107.2.1
 CITY AMENDMENTS.
  
 5- PERSON RESPONSIBLE FOR THE DESIGN OF THE A/C PLAN TO
 PROVIDE NAME AND SIGNATURE. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 6- SIZE OF TRANSFER DUCT FOR BEDROOM #3 DOESN'T COMPLY
 WITH EXCEPTION #3 OF SECTION M1602.4 OF 2010
 FBC-RESIDENTIAL.
  