| Plan Review Notes For Permit 13080425 |
| Permit Number |
13080425 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-28 18:39:01 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRIC | | | | | | 1) SHOW THE LOCATION OF THE METER AND THE PANEL ON THE | | | FLOOR PLAN. NEC 240.24 | | | | | | 2) SHOW COMPLIANCE WITH NEC 230.70 FOR SERVICE | | | DISCONNECTING MEANS. | | | | | | 3) SHOW THE LOCATION OF THE WATER HEATER AND DISCONNECT | | | ON THE FLOOR PLAN. NEC 422.30 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|