2013-08-28 18:39:012010 FBC / 2008 NEC
  
 DENIED BY ELECTRIC
  
 1) SHOW THE LOCATION OF THE METER AND THE PANEL ON THE
 FLOOR PLAN. NEC 240.24
  
 2) SHOW COMPLIANCE WITH NEC 230.70 FOR SERVICE
 DISCONNECTING MEANS.
  
 3) SHOW THE LOCATION OF THE WATER HEATER AND DISCONNECT
 ON THE FLOOR PLAN. NEC 422.30
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]