2013-08-21 18:04:30RESIDENTIAL (R3) ALTERATION/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1- STAIRS NEED HANDRAILS AS REQUIRED BY SEC. R311.7.7
 OF 2010 FBC-RESIDENTIAL. AND, PROVIDE COMPLETE
 SPECIFICATIONS AND DETAILS TO SHOW COMPLIANCE WITH
 TABLE R301.5 AND R311.7.7.
  
 2- GUARDRAIL MAY BE REQUIRED. SPECIFY ACTUAL HEIGHT OF
 LANDING. SEE SEC. R312. PROVIDE COMPLETE DETAIL AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH TABLE R301.5 AND
 SEC. R312.
  
 3- PROVIDE ACCURATE AND COMPLETE ENERGY CALCULATIONS TO
 MATCH PLANS. (SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY
 CONSERVATION):
 A) THIS IS NO NEW CONSTRUCTION. IT'S EXISTING.
  
 B) CRAWL SPACE NEEDS INSULATION. SEE SEC. 402.4.2 OF
 2010 FBC-ENERGY CONSERVATION AND REVISE.
  
 C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 D) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER'S NAME.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ROOF SHINGLES. NOA 11-1122.04 SUBMITTED WAS
 SUPERSEDED BY MIAMI-DADE. NEED CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND DETAILS. PROVIDE ONLY THE PRODUCT APPROVAL COVER
 PAGE AND PAGE SHOWING THE SPECIFIED CONNECTOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712