| 2013-12-12 14:39:43 | RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- DUROVENT ATTIC VENTILATION SYSTEM: PROVIDE COMPLETE |
| | MANUFACTURER'S SPECIFICATIONS SHOWING SIZE OF VENTS AND |
| | TOTAL NET FREE VENTILATING AREA OF EACH PANEL TO VERIFY |
| | THAT NUMBER OF VENTS SHOWN ON PLANS COMPLY WITH SEC. |
| | R806 OF FBC-RESIDENTIAL AND SEC. 103.2.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR |
| | A) METAL SHINGLE ROOF PRODUCT APPROVAL AS SPECIFIED ON |
| | PLANS. |
| | ***NOA 12-0906.08 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. NEED CURRENT NOA. |
| | |
| | B) ALTERNATE CARRIAGE DOORS AS SPECIFIED ON SHEET A-2. |
| | (REPEAT COMMENT). |
| | |
| | C) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS. |
| | ***NOA 10-0923.03 SUBMITTED WAS SUPERSEDED BY |
| | MIAMI-DADE. NEED CURRENT NOA. (REPEAT COMMENT). |
| | |
| | D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| | AND ALL DETAILS. PROVIDE ONLY THE COVER PAGE AND PAGE |
| | SHOWING THE SPECIFIED CONNECTOR. (REPEAT COMMENT). |
| | |
| | E) HURRICANE SHUTTERS FOR FRENCH DOORS THAT HAVE NO |
| | IMPACT GLASS (REPEAT COMMENT). |
| | |
| | 3- ENGINEER OF RECORD TO APPROVE IN WRITING ABOVE |
| | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION |
| | SCHEDULE FOR DOORS THAT HAVE NO IMPACT GLASS. SEC. |
| | 107.2.1 CITY AMENDMENTS. (REPEAT COMMENT). |
| | |
| | 5- ENERGY CALCULATIONS SUBMITTED: OWNER/AGENT TO |
| | CERTIFY AND DATE AT BOTTOM FORM AS REQUIRED BY SEC. |
| | 103.2.3.2 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |