Plan Review Notes
Plan Review Notes For Permit 13080413
Permit Number 13080413
Review Stop B
Sequence Number 1
Notes
Date Text
2013-10-18 16:29:48RESIDENTIAL (R3) ADDITION, BUILDING REVIEW COMMENTS.
 CODE; 2010 FBC.
  
 1- PROVIDE ENERGY CALCULATIONS. SEC. 103.2.1 OF 2010
 FBC-ENERGY CONSERVATION. PLEASE MAKE SURE ALL THE
 INFORMATION IS PROVIDED ND COORDINATED WITH THE PLANS
 SUBMITTED. AND, PREPARER AND OWNER/AGENT TO CERTIFY AND
 DATE BOTTOM OF FORM.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- FRENCH DOORS SHOWN ON PROPOSED SECOND FLOOR PLAN ON
 SHEET A-1 DON'T MATCH FRENCH DOORS SHOWN ON PROPOSED
 NORTH ELEVATION ON SHEET A-2. REVISE AS REQUIRED TO
 MATCH. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 4-PROVIDE COMPLETE FRAMING DETAILS FOR THE ATTACHMENT
 OF THE FRENCH DOORS TO THE STEEL COLUMN AS SHOWN ON
 SHEET A-1 ON THE PROPOSED GARAGE PLAN. SEC. 107.2.1.3
 CITY AMENDMENTS TO FBC.
  
 5- SHEET A-1:
 A) SPECIFY DIMENSION BY STAIRWAY ON TOP LANDING. SEC.
 R311.7.5.
  
 B) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR GUARDRAIL ON INSIDE OPEN BALCONY ON SECOND FLOOR TO
 SHOW COMPLIANCE WITH TABLE R301.5 AND SEC. R312.
  
 C) PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS
 FOR ALL THE EXTERIOR ENTRY CANOPIES SHOWN ON THE
 ELEVATIONS AND FOR THE OPTIONAL CANOPY AS SPECIFY ON
 THE PROPOSED SECOND FLOOR PLAN. SEC. 107.2.1.3 CITY
 AMENDMENTS.
  
 D) PROVIDE COMPLETE STAIR AND HANDRAILS DETAILS AND
 SPECIFICATIONS SHOWING COMPLIANCE WITH SEC. R311.7.4
 AND SEC. R311.7.7.
  
 6- SHEET A-4:
 A) SPECIFY UNDER-STAIR PROTECTION AS REQUIRED BY SEC.
 R302.7.
  
 B) REVISE/CLARIFY NOTE #1 SHOWN ON PROPOSED SOUTH
 ELEVATION CEILING ABOVE THE WASHER AND DRYER.
  
 C) SPECIFY INSULATION ON WALLS, FLOOR BETWEEN GARAGE
 AND SECOND FLOOR, AND ATTIC. ALSO, COORDINATE WITH THE
 ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY
 CONSERVATION.
  
 7- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806.
  
 8- SPECIFY ATTIC ACCESS LOCATION AND SIZE AS REQUIRED
 BY SEC. R807.
  
 9- SPECIFY CARBON MONOXIDE ALARM AS REQUIRED BY SEC.
 R315.1
  
 10- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 11- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND ALL DESIGN
 PROFESSIONAL FEES. SEC. 109.3 CITY AMENDMENTS.
 VALUATION WAS UPDATED TO $68,828. THE PERMIT FEE
 BALANCE IS $1804.30.
  
 12- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR
 A) METAL SHINGLE ROOF PRODUCT APPROVAL AS SPECIFIED ON
 PLANS..
  
 B) ALTERNATE CARRIAGE DOORS AS SPECIFIED ON SHEET A-2
  
 C) FRENCH DOORS WITH SIDELITES AS SHOWN ON PLANS FOR
 PROPOSED SECOND FLOOR.
  
 D) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. PROVIDE ONLY THE COVER PAGE AND PAGE
 SHOWING THE SPECIFIED CONNECTOR.
  
 E) GARAGE DOOR. NOA 12-0125.09 EXPIRED ON AUGUST 21,
 2013. NEED CURRENT NOA.
  
 F) FRENCH DOORS NOA 10-0923.03 SUBMITTED WAS SUPERSEDED
 BY MIAMI-DADE. VISIT THE MIAMI-DADE WEBSITE AND
 DOWNLOAD CURRENT NOA.
  
 G) HURRICANE SHUTTERS FOR FRENCH DOORS THAT HAVE NO
 IMPACT GLASS (SEE NOA SUBMITTED).
  
 H) "INSWING" ENTRY DOOR FOR GUEST SUITE AS SHOWN ON
 PLANS.
  
 13- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- PROVIDE COMPLETE HURRICANE SHUTTERS INSTALLATION
 SCHEDULE FOR DOORS THAT HAVE NO IMPACT GLASS. SEC.
 107.2.1 CITY AMENDMENTS.
  
 15- COORDINATE SECTION 1/S-6 AND FINISH ELEVATIONS
 SHOWN ON SHEET A-4. NEED TO HAVE 6" MIN. DISTANCE FROM
 EXTERIOR WALL COVERING TO FINISH GRADE. SEE SEC. R704.
 SECTION 1/S-6 SHOWS 4" AT SOUTH SIDE. ***NOTE: FOOTING
 SIZE MAY NEED TO BE ADJUSTED.
  
 16- REVISE SECTION 8/S-7 TO MATCH FOUNDATION PLAN.
 MISSING THE THICKENED EDGE. SEC. 107.2.1 CITY
 AMENDMENTS TO FBC.
  
 17- REVISE SECTION 3/S-6. NEED TO SPECIFY 8D RING SHANK
 NAILS FOR SHEATHING FASTENING IN ALL ROOF ZONES AS
 REQUIRED BY SEC. R803.2.3.1.
  
 18- REVISE CORNER DISTANCE "A" ON THE WIND LOAD
 SCHEDULE ON SHEET S-4. NEED 4'-0" MIN. AS REQUIRED BY
 FOOTNOTE "A" ON FIGURE R301.2(7).
  
 19- DESIGN LOAD SCHEDULE ON SHEET S-4: CLEARLY SPECIFY
 AL LIVE AND DEAD LOADS, INCLUDING THE ATTIC LIVE LOAD
 AS REQUIRED BY TABLE R301.5.
  
 20- PROVIDE COMPLETE FRAMING DETAILS FOR THE
 CONSTRUCTION OF EXTERIOR BALCONY HANDRAILS TO SHOW
 COMPLIANCE WITH TABLE R301.5 AND SEC. R312.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712