| 2013-08-15 19:40:31 | 2010 FBC / 2008 NEC | | | | | | 1) PROVIDE TOTAL HOUSE LOAD CALCULATIONS. NEC 220 & 230 | | | | | | 2) THE CONTINUOUS LOADS ARE NOT AT 125%. NEC 220 & 230 | | | | | | 3) PROVIDE AVAILABLE AMPS FOR AIC RATING OF SERVICE | | | EQUIPMENT. NEC 110.9 | | | | | | 4) THE CLOUDED AREA ON SHEET E1.1 IS NOT LEGIBLE DUE TO | | | PRINTING ERROR. CITY AMENDMENTS 107.2.1 | | | | | | 5) THE POWER PANEL IS MISSING OVERCURRENT PROTECTION. | | | NEC 240 | | | | | | 6) THE 125 AMP PANEL REQUIRES A #6 GROUND. NEC 251.66 | | | | | | 7) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM | | | BONDING. | | | | | | 8) SHOW COMPLIANCE WITH NEC 250.50 FOR GROUNDING AND | | | BONDING ALL AVAILABLE ELECTRODES INCLUDING THE FOOTING | | | STEEL. | | | | | | 9) SHOW COMPLIANCE WITH NEC 210.11 FOR 20 AMP BATHROOM | | | CIRCUITS. | | | | | | 10) PROVIDE VOLTAGE DROP CALCULATIONS FOR PANEL 'C' | | | CONDUCTORS TO PROPERLY SIZE GROUNDING CONDUCTOR. NEC | | | 250.3 | | | | | | 11) SMOKE AND CARBON MONOXIDE DETECTORS SHOULD BE | | | LOCATED TO PROVIDE THE BEST AND MOST EFFICIENT LOCATION | | | IN ACCORDANCE WITH LISTING TO PROTECT LIFE. NEC 110.3 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|