Plan Review Notes
Plan Review Notes For Permit 13080391
Permit Number 13080391
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-15 19:40:312010 FBC / 2008 NEC
  
 1) PROVIDE TOTAL HOUSE LOAD CALCULATIONS. NEC 220 & 230
  
 2) THE CONTINUOUS LOADS ARE NOT AT 125%. NEC 220 & 230
  
 3) PROVIDE AVAILABLE AMPS FOR AIC RATING OF SERVICE
 EQUIPMENT. NEC 110.9
  
 4) THE CLOUDED AREA ON SHEET E1.1 IS NOT LEGIBLE DUE TO
 PRINTING ERROR. CITY AMENDMENTS 107.2.1
  
 5) THE POWER PANEL IS MISSING OVERCURRENT PROTECTION.
 NEC 240
  
 6) THE 125 AMP PANEL REQUIRES A #6 GROUND. NEC 251.66
  
 7) SHOW COMPLIANCE WITH NEC 250.94 FOR INTERSYSTEM
 BONDING.
  
 8) SHOW COMPLIANCE WITH NEC 250.50 FOR GROUNDING AND
 BONDING ALL AVAILABLE ELECTRODES INCLUDING THE FOOTING
 STEEL.
  
 9) SHOW COMPLIANCE WITH NEC 210.11 FOR 20 AMP BATHROOM
 CIRCUITS.
  
 10) PROVIDE VOLTAGE DROP CALCULATIONS FOR PANEL 'C'
 CONDUCTORS TO PROPERLY SIZE GROUNDING CONDUCTOR. NEC
 250.3
  
 11) SMOKE AND CARBON MONOXIDE DETECTORS SHOULD BE
 LOCATED TO PROVIDE THE BEST AND MOST EFFICIENT LOCATION
 IN ACCORDANCE WITH LISTING TO PROTECT LIFE. NEC 110.3
  