| Plan Review Notes For Permit 13080308 |
| Permit Number |
13080308 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-13 10:55:02 | 2010 FBC | | | | | | 1) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE | | | STRUCTURAL WINDOW MULLIONS AS REQUIRED BY DCA RULE | | | 9N-3. | | | | | | 2) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED | | | TO INSTALL THE ENTEGRA "GALENA" ROOF TILE (NOA NO. | | | 10-0707.01). IF MECHANICAL FASTENERS ARE USED SPECIFY | | | THE TYPE AND NUMBER OF FASTENERS PER TILE. IF MORTAR OR | | | ADHESIVE IS USED SUBMIT TWO COPIES OF THE PRODUCT | | | APPROVALS AS REQUIRED BY DCA RULE 9N-3. FBCR 301.2.1 | | | | | | 3) THE PRODUCT APPROVALS REQUIRED BY DCA RULE 9N-3 ARE | | | REQUIRED TO BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD. CITY AMENDMENTS 107.3.4.1 | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|