Plan Review Notes
Plan Review Notes For Permit 13080302
Permit Number 13080302
Review Stop R
Sequence Number 2
Notes
Date Text
2013-11-02 08:57:30SEE BUILDING PROVISO
  
 1) PRODUCT APPROVAL COVER SHEET FL 1654-R12 HAS THE
 EVALUATION REPORT FOR FL 1654-R11 ATTACHED TO IT RATHER
 THAN THE R-12 (REVISION 12) ONE. THE W-6 SYSTEM NUMBER
 IS MARKED ON THE R11 REPORT. THIS IS SYSTEM TYPE A-2:
 MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION
 AND BONDED ROOF COVER. THE ANCHOR SHEET ATTACHMENT IS 6
 " OC IN THE 4" LAP AND 6" OC IN FOUR EQUALLY SPACED
 STAGGERED CENTER ROWS FOR A MAXIMUM DESIGN PRESSURE OF
 -60 PSF. THE SIGNED AND SEALED RAS 117 CALCULATIONS
 THAT WERE SUBMITTED SPECIES 2 CENTER ROWS WITH A
 FASTENER SPACING OF 9 " OC . THE LAP AND DESIGN
 PRESSURES MATCH, BUT THE CENTER ROWS ARE DIFFERENT.
 THERE IS NO WAY FOR ME TO DETERMINE WHICH ONE IS
 INCORRECT, BECAUSE THE RAS 117 CALCULATIONS DO NOT
 SPECIFY THE PRODUCT APPROVAL NUMBER OR THE SYSTEM. THE
 CALCULATIONS ALSO DO NOT SPECIFY THE WIND SPEED, THE
 EXPOSURE CATEGORY OR THE MEAN ROOF HEIGHT USED TO
 DETERMINE THE REQUIRED COMPONENT AND CLADDING
 PRESSURES. PLEASE CORRECT.
  
 THE FOLLOWING ROOFING PRODUCTS ARE ACCEPTABLE: NOA NO.
 12-0529.12 FOR THE CLAY BARREL TILE AND NOA NO.
 12-0228.18 FOR THE AH-160 ROOF TILE ADHESIVE