| Plan Review Notes For Permit 13080302 |
| Permit Number |
13080302 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-11-02 08:57:30 | SEE BUILDING PROVISO | | | | | | 1) PRODUCT APPROVAL COVER SHEET FL 1654-R12 HAS THE | | | EVALUATION REPORT FOR FL 1654-R11 ATTACHED TO IT RATHER | | | THAN THE R-12 (REVISION 12) ONE. THE W-6 SYSTEM NUMBER | | | IS MARKED ON THE R11 REPORT. THIS IS SYSTEM TYPE A-2: | | | MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION | | | AND BONDED ROOF COVER. THE ANCHOR SHEET ATTACHMENT IS 6 | | | " OC IN THE 4" LAP AND 6" OC IN FOUR EQUALLY SPACED | | | STAGGERED CENTER ROWS FOR A MAXIMUM DESIGN PRESSURE OF | | | -60 PSF. THE SIGNED AND SEALED RAS 117 CALCULATIONS | | | THAT WERE SUBMITTED SPECIES 2 CENTER ROWS WITH A | | | FASTENER SPACING OF 9 " OC . THE LAP AND DESIGN | | | PRESSURES MATCH, BUT THE CENTER ROWS ARE DIFFERENT. | | | THERE IS NO WAY FOR ME TO DETERMINE WHICH ONE IS | | | INCORRECT, BECAUSE THE RAS 117 CALCULATIONS DO NOT | | | SPECIFY THE PRODUCT APPROVAL NUMBER OR THE SYSTEM. THE | | | CALCULATIONS ALSO DO NOT SPECIFY THE WIND SPEED, THE | | | EXPOSURE CATEGORY OR THE MEAN ROOF HEIGHT USED TO | | | DETERMINE THE REQUIRED COMPONENT AND CLADDING | | | PRESSURES. PLEASE CORRECT. | | | | | | THE FOLLOWING ROOFING PRODUCTS ARE ACCEPTABLE: NOA NO. | | | 12-0529.12 FOR THE CLAY BARREL TILE AND NOA NO. | | | 12-0228.18 FOR THE AH-160 ROOF TILE ADHESIVE |
|