| 2013-10-21 16:12:22 | 2010 FBC |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PROJECTED ROOF AREA IN THE CALCULATIONS FOR THE |
| | ROOF SCUPPERS ON SHEET A-3 ARE REQUIRED TO INCLUDE ONE |
| | HALF OF VERTICAL WALL AREAS THAT DIVERT ( FBC P 1106.4) |
| | RAINWATER TO THE ROOF AND THE AREA OF THE ROOFS ABOVE |
| | THAT WILL DRAIN ON TO THE LOWER ROOF. FBCR 903.4, FBC P |
| | 1101.7 AND 1106.4 PLEASE REVISE CALCULATIONS. |
| | |
| | 2) SPECIFY THE EMBED DEPTH OF THE SLEEVE ANCHORS ON THE |
| | CANOPY DETAIL, 4 ON SHEET A-10. FBC R301.2.1 |
| | |
| | 3) ALSO, ON DETAIL 4 ON A-10, PLEASE REVIEW THE |
| | ATTACHMENT OF THE RAFTERS TO THE BEAM WITH TWO (2) 10D |
| | TOE-NAILS FOR REQUIRED UPLIFT RESISTANCE. FBC R301.2.1 |
| | |
| | 4) SUBMIT TWO SETS OF SPECIFICATIONS AND THE LISTING |
| | INFORMATION FOR THE ISOKERN FIREPLACES AND THEIR METAL |
| | FLUE CHIMNEYS. FBC R1001, R1004 AND R1005. |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R1006 FOR REQUIRED EXTERIOR |
| | AIR SUPPLY. |
| | |
| | 6) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | CLAY BARREL TILE ROOF (NOA NO. 11-0329.02) EXPIRED ON |
| | 3/13/13. SUBMIT TWO COPIES OF CURRENT PRODUCT |
| | APPROVALS. DCA RULE 9N-3 |
| | |
| | 7) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED |
| | TO INSTALL THE ROOF TILE BY MARKING ONE OF THE ONES |
| | LISTED IN THE PRODUCT APPROVAL. FBC R905.3.7 IF AN |
| | ADHESIVE IS SELECTED, SUBMIT TWO COPIES OF THE PRODUCT |
| | APPROVAL FOR IT. DCA RULE 9N-3 |
| | |
| | 8) SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR THE |
| | FLAT ROOFS AND DECK AREAS AS REQUIRED BY DCA RULE 9N-3. |
| | SUBMIT TWO SETS OF SIGNED AND SEALED RAS 117 |
| | CALCULATIONS FOR ENHANCED FASTENING AT THE PERIMETER |
| | AND CORNER AREAS (LIMITATION #7) IF THE MAXIMUM DESIGN |
| | PRESSURE IS NOT ADEQUATE FOR THE FASTENING OPTION THAT |
| | IS SELECTED. FBC R301.2.1 |
| | |
| | 9) THE REQUIRED DESIGN PRESSURES FOR THE OVERHEAD |
| | GARAGE DOOR IS SPECIFIED ON THE PLAN AS + 48 , - 62 |
| | PSF. THE AMARR GARAGE DOOR PRODUCT APPROVAL THAT WAS |
| | SUBMITTED (NOA NO. 12-0228.12) HAS A NEGATIVE DESIGN |
| | PRESSURE OF - 60.3 PSF WHICH IS LOWER THAN THE REQUIRED |
| | NEGATIVE PRESSURE LISTED ON THE PLANS. PLEASE SUBMIT |
| | PRODUCT APPROVALS WITH ADEQUATE PRESSURES. FBC R301.2.1 |
| | |
| | 10) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | PGT FIXED WINDOW (NOA NO. 11-1110.15) HAS BEEN |
| | SUPERSEDED. SUBMIT TWO COPIES OF CURRENT PRODUCT |
| | APPROVALS. DCA RULE 9N-3 |
| | |
| | 11) THE PRODUCT APPROVALS THAT WERE SUBMITTED FOR THE |
| | EXTERIOR FRENCH DOORS (FL# 16217.1) ARE FOR CGI SERIES |
| | SENTINEL 160 DOORS. THE DOOR NOTES ON SHEET A-12 |
| | SPECIFY PGT FD750 SERIES DOORS. PLEASE CLARIFY. CITY |
| | AMENDMENTS 107.2.1 |
| | |
| | 12) SUBMIT TWO COPIES OF THE PRODUCT EVALUATION FOR THE |
| | ICYNENE SPRAY FOAM INSULATION. FBC R316 |
| | |
| | IN ORDER TO EXPEDITE THE PLAN REVIEW, PLEASE SUBMIT A |
| | RESPONSE LETTER INDICATING HOW EACH OF THE PLAN REVIEW |
| | COMMENTS HAVE BEEN ADDRESSED. |
| | |