| Notes |
| Date |
Text |
| 2013-08-12 15:56:00 | ONLY ONE SET OF PLANS PROVIDED. SCOPE OF WORK IS NOT | | | CLEAR. DEFINE WHAT AND HOW MUCH IS BEING INSTALLED, | | | REPLACED OR OTHERWISE. HOW MANY UNITS ARE ON THE | | | PROPERTY? PROVIDE A RISER DIAGRAM, PANEL LOCATIONS, | | | CIRCUIT DIRECTORY, LOAD CALCULATION, AVAILABLE FAULT | | | CURRENT, AFCI, GFCI PROTECTION, PANEL DIRECTORY, | | | EXTERIOR RECPTACLES, ROOM DESIGNATIONS, ETC. SO PLAN | | | AND OTHER INFORMATION CAN BE EVALUATED. ADDITIONAL | | | INFORMATION MAY BE REQUESTED UPON RESUBMISSION IF THAT | | | INFORMATION IS FOUND TO CREATE ADDITIONAL QUESTIONS OR | | | IS NOT IN COMPLIANCE WITH THE GOVERNING REGULATIONS. DH |
|