Plan Review Notes
Plan Review Notes For Permit 13080279
Permit Number 13080279
Review Stop M
Sequence Number 3
Notes
Date Text
2015-01-13 14:20:44RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS
 TO NEW INFORMATION SUBMITTED.
 CODE: 2010 FBC.
  
 1- A) EQUIPMENT SIZING CALCULATIONS SUBMITTED NEED TO
 BE DONE WITH AN APPROVED HEATING AND COOLING
 CALCULATIONS METHOD AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION AND SEC. M1401.3 OF 2010
 FBC-RESIDENTIAL. CALCULATIONS SUBMITTED ARE NOT AN
 APPROVED METHOD.
  
 B) EQUIPMENT SIZING CALCULATIONS METHOD NEED TO BE DONE
 BASED ON BUILDING LOADS FOR THE DIRECTIONAL ORIENTATION
 OF THE BUILDING AS REQUIRED BY SEC. 403.6.1 OF 2010
 FBC-ENERGY CONSERVATION.
  
 C) EQUIPMENT SIZING CALCULATIONS INTERIOR DESIGN
 CONDITIONS NEED TO COMPLY WITH SEC. 302.1 OF 2010
 FBC-ENERGY CONSERVATION.
  