2014-04-18 11:55:42RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS
 TO NEW INFORMATION SUBMITTED.
 CODE: 2010 FBC.
  
 1- EQUIPMENT SIZING CALCULATIONS WERE CROSSED DOWN AS
 OLD. NO NEW EQUIPMENT SIZING CALCULATIONS WERE
 SUBMITTED. PROVIDE NEW EQUIPMENT SIZING CALCULATIONS.
 SEC. 403.6 OF 2010 FBC-ENERGY CONSERVATION.
  
 2- INFORMATION ON ITEMS #12 AND #13 OF THE ENERGY
 CALCULATIONS DON'T MATCH INFORMATION SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS (OLD ONES). COORDINATE
 WITH ITEM #1 ABOVE AND REVISE AS REQUIRED TO MATCH.
 SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 3- EQUIPMENT INFORMATION SHOWN ON THE EQUIPMENT SIZING
 CALCULATIONS NEED TO MATCH EQUIPMENT INFORMATION SHOWN
 ON THE A/C PLAN. REVISE AS REQUIRED TO MATCH. SEC.
 103.2.2 OF 2010 FBC-ENERGY CONSERVATION.
  
 4- A/C PLAN SUBMITTED:
 A) HOW MANY AHU UNITS #1 ARE THERE?. THERE IS ONE IN
 THE MAIN HOUSE AND ANOTHER ONE IN THE CABANA. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 B) WHY ARE THERE TWO AIR HANDLER UNITS SHOWN ON THE
 CABANA? AIR HANDLER UNIT #1 AND AIR HANDLER UNIT #2.
 SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 C) AIR HANDLER UNIT #1 (MAIN HOUSE) AND #2 (CABANA)
 NEED TO COMPLY WITH SEC. M1305.1. SHOW ACCESSS
 COMPLIANCE.
  
 D) CABANA FIRST FLOOR: INFORMATION SHOWN FOR THE A/C
 RETURN AIR IS NOT CLEAR. FIRST FLOOR SHOWS A/C RETURN
 AND ATTIC ACCESS ON THE SAME SPOT. SECOND FLOOR SHOWS
 AHU #2, BUT NOT ATTIC ACCES. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712