| 2014-04-24 14:04:11 | SECOND ELECTRICAL REVIEW FAILED. IT IS NOT THE INTENT |
| | OF THIS REVIEWER TO GENERATE A PUNCH LIST BUT FOLLOWING |
| | IS A LIST OF ITEMS NEEDING ATTENTION: |
| | 1. THERE IS A MISSING LIGHT OUTSIDE THE CABANA STAIRS |
| | (ENTRANCE) |
| | 2. THE STAIRWAY SHALL BE PROPERLY ILLUMINATED AND |
| | SWITCHED AT BOTH THE TOP AND BOTTOM |
| | 3. IT APPEARS THAT THE AHU'S ARE INSIDE THE ATTIC BOTH |
| | IN THE CABANA & MAIN HOUSE. IF THIS IS THE CASE, |
| | SPECIFIC OUTLET, LIGHTING AND ACCESS REQUIREMENTS SHALL |
| | BE MET. SEE NEC 110.33 (B) ACCESS. PERMANENT LADDERS OR |
| | STAIRWAYS SHALL BE PROVIDED |
| | TO GIVE SAFE ACCESS TO THE WORKING SPACE AROUND |
| | ELECTRICAL EQUIPMENT INSTALLED ON PLATFORMS, BALCONIES, |
| | OR MEZZANINE FLOORS OR IN ATTIC OR ROOF ROOMS OR |
| | SPACES. |
| | 4. SHOW THE LOCATION OF BOTH PANELS, THE CABANA & MAIN |
| | HOUSE ON THE FLOOR PLAN. |
| | 5. SHOW THE LOCATION OF THE MAIN SERVICE, METER & MAIN |
| | DISCONNECT ON THE FLOOR PLAN. |
| | 6. NEC 210.12 HAS BROADER AFCI REQUIREMENTS THAN THOSE |
| | REFLECTED ON THE PANEL SCHEDULE. CORRECT ACCORDINGLY. |
| | 7. INDICATE IF THE SUBMITTED LOAD CALC ARE FOR THE |
| | WHOLE PROPERTY AND IF NOT, SHOW THE LOAD CALCS FOR THE |
| | CABANA. |
| | 8. THE METER SOCKET SHOWN ON THE PLANS IS A 100 AMP, |
| | REPLACE TO MATCH LOAD. |
| | 9 THE EXTERIOR REAR LIGHTING SHOULD BE SWITCHED FROM |
| | BOTH THE KITCHEN AND THE MASTER BEDROOM. |
| | |
| | FOR ANY QUESTIONS OR COMMENTS ON THIS REVIEW, PLEASE |
| | CONTACT: |
| | MIKE ALBARRAN, ELECTRICAL PLANS EXAMINER, PX3353 |