2014-04-14 16:00:55RESIDENTIAL (R3) ADDITION, SECOND BUILDING REVIEW
 CHECKLIST.
 CODE: 2010 FBC.
  
 1- PLANS NEED ENGINEER'S ORIGINAL SEAL AND SIGNATURE.
 CHAPTER 61G15-23.002. DIGITAL SIGNATURE IS ONLY FOR
 ELECTRONICALLY TRANSMITTED PLANS.
  
 2- SHEET S-1:
 A) CLARIFY/REVISE FOOTING F3 SPECIFIED FOR THE NEW
 TRELLIS. SEC. R301 OF 2010 FBC-RESIDENTIAL.
  
 B) REVISE STRUCTURAL NOTE #10: (1)BUILDING EXPOSURE IS
 "C" NOT "B". SEC. R301.2.1.4.3.
  
 3- A) UPDATE SOIL TEST REPORT TO INCLUDE THE PROPOSED
 TWO STORY CONCRETE BLOCK ADDITION. TEST REPORT
 SUBMITTED IS FOR THE SINGLE STORY ADDITION ONLY. NEED
 ADDITIONAL TEST BORINGS ON THE TWO STORY ADDITION
 LOCATION. SEC. R401.4.
  
 B) PROVIDE 2 COPIES. ONLY ONE WAS SUBMITTED AT THIS
 TIME.
  
 4- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR SINGLE
 CASEMENT WINDOWS SIZES AS SHOWN ON WINDOW SCHEDULE FOR
 BEDROOM #1 AND STUDY (50' X 50" AND 62" X 50"). NOA
 12-1220.14 SUBMITTED DOESN'T INCLUDE THESE SIZES.
 WINDOW SCHEDULE SPECIFIES "SINGLE CASEMENT TO LOOK LIKE
 SINGLE HUNG". NEED TO SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.
  
 5- ATTIC ACCESS SIZE SPECIFIED FOR THE ONE STORY
 ADDITION AND THE TWO STORY ADDITION DON'T COMPLY WITH
 SEC. R807. REVISE AS REQUIRED.
 ***NOTE: BE AWARE THAT LOCATION OF A/C UNITS NEED TO
 COMPLY WITH SEC. M1305 OF 2010 FBC-RESIDENTIAL.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS
 AND ALL DETAILS. ***NOTE: PROVIDE ONLY THE PRODUCT
 APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED
 CONNECTOR. (NOT SUBMITTED).
  
 B) OVERHEAD GARAGE DOOR. NOA 08-0320.05 SUBMITTED
 EXPIRED ON AUGUST 21/2013. NEED CURRENT NOA.
  
 C) CONCRETE ROOF TILE ADHESIVE. NOA 12-0228.18
 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. NEED CURRENT
 NOA. VISIT THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT
 NOA.
  
 D) SHUTTERS SHOWN ON PROPOSED CABANA WEST ELEVATION.
 AND, PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 ABOVE PRODUCT APPROVALS AS REQUIRED BY SEC. 107.3.4.1
 OF CITY AMENDMENTS.
  
 8- PROVIDE MANUFACTURER'S ICC EVALUATION REPORT FOR THE
 NEW ICYNENE INSULATION SPECIFIED ON PLANS TO VERIFY
 COMPLIANCE WITH ENERGY CALCULATIONS REQUIREMENTS AND
 INSULATION LIMITATIONS. SEC. 107.2.1 CITY AMENDMENTS.
  
 9- ENGINEER TO REVISE CALCULATIONS ON SHEET S-7:
 A) BUILDING EXPOSURE IS "C" NOT "B". SEC. R301.2.1.4.3.
  
 B) THE NOMINAL WIND SPEED FOR THE CITY OF WEST PALM
 BEACH IS 132MPH NOT 131.7. R301.2.1.4.3.
  
 C) REVISE THE WINDOWS AND DOORS DESIGN PRESSURES. NEED
 DESIGN PRESSURES ACCORDING TO EXPOSURE "C" AND
 ACCORDING TO THE MEAN ROOF HEIGHT OF EACH BUILDING. TWO
 STORY ADDITION AND ONE STORY ADDITION. SEC.
 R301.2.1.4.3
 ***NOTE: COORDINATE WITH DESIGN PRESSURES SHOWN ON
 WINDOW AND DOOR SCHEDULE ON SHEET A400.
  
 10- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE MAIN
 HOUSE AND PROVIDE 2 COPIES. ONLY ONE COPY WAS SUBMITTED
 (SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION):
 A) ENGINEER DOING THE CALCULATIONS NEED TO SIGN AND
 SEAL THEM WITH ORIGINAL SEAL AND SIGNATURE AS REQUIRED
 BY CHAPTER 471. DIGITAL SIGNATURE ONLY APPLIES TO
 ELECTRONICALLY SUBMITTED DOCUMENTS, NOT HARD COPY
 DOCUMENTS.
  
 B) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH TO
 MATCH PLANS. (REPEAT COMMENT).
  
 C) REVISE WINDOW INFORMATION ON SHEET 3 OF 5 TO MATCH
 PLANS AND PRODUCT APPROVALS. . THERE ARE NOT WOOD
 WINDOWS. AND, REVISE THE OVERHANG DEPTH AND SEPARATION
 TO MATCH PLANS.
  
 D) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
  
 E) COMPLETE ALL THE INFORMATION ON TOP OF FORM,
 INCLUDING THE BUILDER NAME, ETC.
  
 F) PROVIDE MANUFACTURER'S SPECS SHOWING HOW PROVIDING
 R19 INSULATION ON THE DUCTS AS SPECIFIED ON ITEM #11.
  
 G) INFORMATION SHOWN ON ITEMS #12 AND #13 TO MATCH
 INFORMATION SHOWN ON THE A/C EQUIPMENT SIZING
 CALCULATIONS. REVISE AS REQUIRE TO MATCH.
  
 11- REVISE ENERGY CALCULATIONS SUBMITTED FOR THE CABANA
 AND PROVIDE 2 COPIES. ONLY ONE COPY WAS SUBMITTED.
 (SEC. 103.2.1.1.2 OF 2010 FBC-ENERGY CONSERVATION):
 A) SEE COMMENTS TO MAIN HOUSE AND REVISE ALL THAT APPLY
 TO THE CABANA.
  
 B) PROVIDE ICYNENE ICC EVALUATION REPORT SHOWING HOW
 PROVIDING R45 INSULATION IN THE CEILING ASSEMBLY AS
 SHOWN ON ITEM #10..
  
 12- SHEET A100 SHOWS A DOOR FOR THE CABANA STORAGE, BUT
 DOOR SCHEDULE AND ELEVATIONS DON'T SHOW ANY. REVISE AS
 REQUIRED TO MATCH. PROVIDE PRODUCT APPROVAL IF DOOR IS
 GOING TO BE INSTALLED. DCA RULE 9N-3.
  
  
 ***THE FOLLOWING ARE NEW ITEMS BASED ON THE PLANS
 SUBMITTED:
  
 13- STRUCTURAL PLANS SUBMITTED ARE LACKING A LOT OF
 INFORMATION: MAIN HOUSE: NEED COMPLETE FRAMING DETAILS
 AND SPECIFICATION FOR ALL 2X6 ROOF FRAMING MEMBERS
 INCLUDING ALL THE CONNECTORS (CONNECTIONS AT RIDGE
 BEAMS, COLLAR TIES, ETC). NO INFORMATION GIVEN FOR THE
 TRELLIS CONSTRUCTION, NO INFORMATION GIVEN FOR THE
 GATES AND WALL CONSTRUCTION. CLARIFY IF CABANA ROOF
 FRAMING MEMBERS ARE PRE-ENGINEERED TRUSSES OR 2X6 ROOF
 RAFTERS (FRAMING PLANS AND WALL SECTIONS SUBMITTED
 CONTRADICT EACH OTHER). HOW DO YOU SECURE COLLAR TIES
 TO THE WALL WITH SIMPSON HETAL 18 CONNECTORS AS SHOWN
 ON MAIN HOUSE AND CABANA WALL SECTIONS?. ROOF FRAMING
 PLAN #1 ON SHEET S-3 DOESN'T MATCH BUILDING SECTION #1
 ON SHEET S-5 (LOOK AT THE LOCATION OF RIDGE BEAMS).
 CABANA FLOOR FRAMING PLAN: SPECIFY SPACING OF 2X4 STUDS
 ON INTERIOR BEARING WALL AND SPECIFY HEADER SIZES AND
 SUPPORTING POSTS AT DOORS OPENINGS. SEC. R301.1
  
 14- SHEET S-6:
 A) FIRST RISER HEIGHT DOESN'T COMPLY WITH SEC.
 R311.7.4.1.
  
 B) TREADS NEED A NOSING AS REQUIRED BY SEC. R311.7.4.3.
  
 C) SPECIFY HANDRAIL HEIGHT. SEC. R311.7.7.1.
  
 D) FOOTING INFORMATION DOESN'T MATCH FOUNDATION PLAN.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 15- STRUCTURAL DRAWINGS ARE ALSO MISSING THE STRUCTURAL
 BUCK DETAILS FOR GARAGE DOOR, ALL NEW EXTERIOR DOORS
 AND WINDOWS. SEC. R301.1.
 ***NOTE: WHEN SPECIFYING BUCK SIZES TAKE INTO
 CONSIDERATION THAT DOORS AND WINDOWS BUCKS REQUIRE
 FRAME FULL SUPPORT. SEE SEC. R612.10.
  
 *** IN ORDER TO EXPEDITE THE REVIEW PROCESS, PLEASE
 PROVIDE RESPONSE LETTER ADDRESSING EACH ITEM.
  