| Permit Number |
13080279 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-09-09 13:22:10 | FIREST REVIEW 9-9-13 | | | 1. ALL GARAGE RECPTS TO BE GFCI PROTECTED PER NEC | | | 210.8A | | | 2. PROVIDE INTERSYSTEM GROUND BAR AT SERVICE PER NEC | | | 250.94 | | | 3. PLEASE CLARIFY IF CABANA IS ONE STORY OR TWO. THERE | | | IS CONFLICTING INFORMATION ON A-001 AND OTHER DRAWINGS | | | 4. PROVIDE CORCUITS FOR ELECTRICAL DEVICES | | | 5. CLRIFY SUB-PANEL FEEDERS. #3, #4, #8 ??? IF RUN UG | | | MUST BE THWN. | | | 6. CABANA WH BREAKER SHOULD BE 20A | | | END OF REVIEW |
|