Plan Review Notes
Plan Review Notes For Permit 13080279
Permit Number 13080279
Review Stop B
Sequence Number 1
Notes
Date Text
2013-09-13 14:47:33RESIDENTIAL (R3) ADDITION/RENOVATION BUILDING REVIEW
 COMMENTS.
 CODE: 2010 FBC.
  
 1-PLANS SUBMITTED ARE INCOMPLETE. MISSING:
 *A)FOUNDATION PLANS, ** B)CABANA SECOND FLOOR FRAMING
 PLAN, ***C)ALL ROOF FRAMING PLANS, INCLUDING THE
 CONVENTIONAL 2X6 ROOF FRAMING PLAN FOR PROPOSED
 ADDITION. SPECIFY ALL FRAMING MEMBERS AND CONNECTORS.
 ****D) COMPLETE STRUCTURAL WALL SECTIONS WITH DETAILS
 AND SPECIFICATIONS, INCLUDING THE BALCONY.
 *****E)COMPLETE INFORMATION FOR THE DECK AND TRELLIS:
 FOOTINGS, FRAMING PLANS, CONNECTORS, ******F)PLANS
 SHOWING SIZE OF ALL STRUCTURAL BEAMS AND LINTELS. ETC.
 SEC. 107.3.5.3 OF CITY AMENDMENTS TO FBC.
  
 2- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH
 COUNTY (2300 N. JOG RD.) TO VERIFY IF IMPACT FEES ARE
 DUE. BRING BACK COUNTY STAMPED PLANS AND COPY OF PAID
 RECEIPT IF FEES ARE DUE. REQUIRED BY THE COUNTY IMPACT
 FEE ORDINANCE OF THE UNIFIED LAND DEVELOPMENT CODE.
  
 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS,
 CONTRACTOR'S OVERHEAD AND PROFIT AND DESIGN
 PROFESSIONAL FEES. VALUATION WAS UPDATED TO $149,376.
 THE PERMIT FEE BALANCE IS $3661.12.
  
 4- PLANS TO SPECIFY ALL DESIGN CRITERIA: *A)CURRENT
 BUILDING CODE. B)ALL DEAD LOADS, LIVE LOADS, ATTIC LIVE
 LOADS, SECOND FLOOR LOADS, ROOF LOADS, BALCONY LOADS,
 STAIRWAY LOADS, WIND LOADS AS REQUIRED BY SEC. R301.1
 AND TABLE R301.5 OF 2010 FBC-RESIDENTIAL.
 ***NOTE: ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING
 IS LOCATED IN EXPOSURE "C".
  
 5- PROVIDE COMPLETE DETAILS, SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE CABANA STAIRS AND HANDRAILS TO SHOW
 COMPLIANCE WITH SEC. R311.7 AND TABLE R301.5.
  
 6- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO
 THE LIVING ROOM SHOWING COMPLIANCE WITH THE FIRE RATING
 OF SEC. R302.5.1.
  
 7- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR THE
 REINFORCING OF THE PROPOSED OPENING ON THE MASONRY WALL
 LEADING FROM THE DINING ROOM TO THE NEW KITCHEN. SEC.
 107.2.1 CITY AMENDMENTS TO FBC.
  
 8- SHEET A100: CABANA FIRST FLOOR PLAN: OPENING SIZE
 SHOWN FOR FIRST FRENCH DOORS DON'T MATCH INFORMATION
 SHOWN ON EXTERIOR ELEVATION. REVISE AS REQUIRED. SEC.
 107.2.1 CITY AMENDMENTS.
  
 9- SPECIFY CARBON MONOXIDE ALARMS FOR ALL BEDROOMS.
 SEC. R315.
  
 10- PROVIDE SOIL TEST REPORT. SEC. R401.4.
  
 11- PROVIDE MANUFACTURER CUT SHEETS FOR BEDROOM #1 AND
 STUDY WINDOWS TO SHOW COMPLIANCE WITH THE EGRESS
 REQUIREMENTS OF SEC. R310.
  
 12- EXISTING HOUSE WAS DESIGNED TO HAVE SHINGLES
 ROOFING, ENGINEER OF RECORD TO PROVIDE ANALYSIS SHOWING
 THAT PROPOSED ROOF FRAMING AND CONCRETE TILE WILL BE
 ADEQUATELY SUPPORTED BY THE EXISTING STRUCTURE. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 13- SPECIFY ATTIC ACCESS LOCATION AND SIZE ON THE NEW
 ADDITION. SEC. R807.
  
 14- FIRST FLOOR CABANA SHOWS "POOL STO" INSIDE THE
 CLOSET OF THE HABITABLE AREA. CLARIFY WHAT KIND OF POOL
 STORAGE IS INTENDED TO BE TO VERIFY IF ADDITIONAL
 SAFETY REQUIREMENTS WILL BE REQUIRED. SEC. 107.2.1 CITY
 AMENDMENTS.
  
 15- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHUTTERS AS SHOWN ON EXTERIOR ELEVATIONS. AND,
 PROVIDE COMPLETE INSTALLATION SCHEDULE.
  
 B) INSWING WOOD ENTRY DOOR AS SHOWN ON PLANS.
  
 C) CABANA WOOD ENTRY AND STORAGE DOORS AS SHOWN ON
 PLANS. INCLUDING THE ARCHED ONE.
  
 D) ALL SIMPSON (OR ANY OTHER) STRUCTURAL CONNECTORS
 SPECIFIED ON PLANS AND ALL DETAILS. ***NOTE; PROVIDE
 ONLY THE PRODUCT APPROVAL COVER PAGE AND PAGE SHOWING
 THE SPECIFIED CONNECTOR.
  
 E) PRECAST LINTELS AS SHOWN ON SECTION 1 ON SHEET A300.
  
 G) ROOF TILE ADHESIVE (IF USED). SEE ROOF TILE NOA FOR
 LISTED ADHESIVES. OR ENGINEER TO PROVIDE ROOF TILE
 FASTENING AS REQUIRED BY SEC. 107.2.1.2 CITY
 AMENDMENTS.
  
 16- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 OF CITY AMENDMENTS.
  
 17- WINDOW A-104 DOESN'T COMPLY WITH EGRESS
 REQUIREMENTS OF SEC. R310.1.2. REVISE AS REQUIRED.
  
 18- A) SCALE OF DRAWING SHOWN ON SHEET A001 DOESN'T
 MATCH SCALE PLANS ARE DRAWN. AND B) SITE PLAN CALLS FOR
 "PROPOSED ONE STORY CABANA". PLANS SHOWN 2 STORY.
 REVISE AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 19- PROVIDE COMPLETE GABLE END DETAIL AS REQUIRED BY
 SEC. R609.4.
  
 20- FINISH FLOOR ELEVATION TO BE 6" ABOVE GRADE AS
 REQUIRED BY SEC R704. INDICATE ON WALL SECTIONS. FINISH
 GRADE TO SHOW COMPLIANCE.
  
 21- SHEET A300:
 A) SECTION 1 DOESN'T SHOW CEILING INSULATION. SEC.
 405.2.1 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) CLARIFY IF ENGINEER IS DESIGNING AN UNVENTED ATTIC
 OR VENTED ATTIC. PROVIDE COMPLETE SPECIFICATIONS
 SHOWING COMPLIANCE WITH SEC. R806.
 ***NOTE: ENERGY CALCULATIONS ARE CALLING FOR VENTED
 ATTIC. INFORMATION ON ENERGY CALCULATIONS AND PLANS
 NEED TO MATCH.
  
 C) NEED TO SPECIFY MIN. 8D RING SHANK NAILS FOR AL ROOF
 ZONES. AND, NEED TO SPECIFY 8D RING SHANK NAILS AT
 4"O.C. IN ROOF ZONE #3 AS REQUIRED BY SEC. R803.2.3.1.
 AND SEE FIGURE R803.2.3.1 FOR MIN. DIMENSION FOR ROOF
 ZONE #3 ON GABLE ENDS.
  
 D) SECTION #2 CALLS FOR "8"X THICKENED EDGE WITH 1#5.
 REVISE AS REQUIRED. THIS CAN'T BE THE SIZE OF FOOTING
 FOR A TWO STORY BUILDING. SEC. 107.2.1 CITY AMENDMENTS.
  
 22- WIND ANALYSIS CALCULATIONS SUBMITTED:
 A) ENGINEER TO PROVIDE ORIGINAL SEAL AND SIGNATURE. NO
 COPIES. AS REQUIRED BY CHAPTER 471 FLORIDA STATUTE.
  
 B) ENGINEER TO CLARIFY BASIC WIND SPEED INDICATED. IS
 THE 107.5174 MPH THE ULTIMATE OR THE NOMINAL WIND
 SPEED. SEC. R301.2.1.3.
  
 C) PROVIDE CALCULATIONS FOR THE 2 STORY CABANA. SEC.
 R301.2.1.3.
  
 D) CLARIFY WHY THE DESIGN PRESSURES FOR COMPONENTS AND
 CLADDING ARE USING AN EFFECTIVE AREA OF 25 S.F... SEE
 FOOT NOTES A AND B ON TABLE R301.2(2) AND REVISE
 ACCORDINGLY.
  
 23- ENERGY CALCULATIONS MAIN HOUSE:
 A) REVISE THE CONDITIONED FLOOR AREA ON ITEM #6. NEED
 TO INCLUDE THE CEILING TRAY AREAS AS REQUIRED BY SEC.
 402.2.13 OF 2010 FBC-ENERGY CONSERVATION.
  
 B) REVISE THE AREA WEIGHTED AVERAGE OVERHANG DEPTH TO
 MATCH PLANS.
  
 C) ITEM #10 CALL FOR VENTED CEILING. COORDINATE WITH
 INFORMATION SHOWN ON PLANS. ALSO, WHERE IS THE SINGLE
 ASSEMBLY LOCATED AT?
  
 D) REVISE ROOF INFORMATION ON SHEET 2 OF 6. ROOF TYPE
 IS NOT FLAT. SEE PLANS.
  
 E) REVISE ATTIC INFORMATION ON SHEET 2 OF 6. THERE IS
 ATTIC. SEE PLANS.
  
 F) REVISE DOOR TYPE, SIZE, ORIENTATION AND NUMBER OF
 DOORS SHOWN ON SHEET 3 OF 6 TO MATCH PLANS AND PRODUCT
 APPROVALS.
  
 G) REVISE WINDOW ORIENTATION ON SHEET 3 OF 6 TO MATCH
 PLANS.
  
 H) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
  
 24- ENERGY CALCULATIONS CABANA:
 A) SEE COMMENTS TO MAIN HOUSE AND REVISE ALL THAT APPLY
 TO THE CABANA.
  
 B) NEED TO SPECIFY AREA AND INSULATION BETWEEN THE TWO
 FLOORS.
  
 C) CEILING INSULATION TO MATCH PLANS.
  
 D) OWNER/AGENT TO CERTIFY AND DATE BOTTOM OF FORM.
  
 E) REVISE THE JURISDICTION NUMBER TO CORRESPOND TO WEST
 PALM BEACH.
  
 25- PROVIDE COMPLETE SPECIFICATIONS ON PLANS SHOWING
 HOW THE CABANA CEILING IS DESIGNED AS UNVENTED. AND
 COORDINATE WITH THE ENERGY CALCULATIONS. SEC. 103.2.2
 OF 2010 FBC-ENERGY CONSERVATION.
  
 26- ENGINEER TO REVISE DOOR SCHEDULE ON SHEET A400.
 THERE ARE NO WOOD DOORS. SEE PRODUCT APPROVALS
 SUBMITTED.
  
 *** IN ORDER TO EXPEDITE THE REVIEW PROCESS, PLEASE
 PROVIDE RESPONSE LETTER ADDRRESING EACH ITEM.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION, PLANS EXAMINER
 (561)805-6712