| Plan Review Notes For Permit 13080231 |
| Permit Number |
13080231 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2014-06-04 14:29:58 | PLUMBING PLAN REVIEW | | | PERMIT: 13080231 | | | ADD: 6651 N JOG RD1ST | | | CONT: CDM | | | TEL: (561 | | | | | | 2010 FLORIDA BUILDING CODE W | | | * 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE, CHAPTER 1, ADMINISTRATION, 2010 EDITION | | | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. | | | | | | 1ST REVIEW | | | DATE: WED JUNE 4/2014 | | | ACTION: DENIED | | | | | | 1002.3 PROHIBITED TRAPS. | | | THE FOLLOWING TYPES OF TRAPS ARE PROHIBITED: | | | | | | 1.TRAPS THAT DEPEND ON MOVING PARTS TO MAINTAIN THE | | | SEAL. | | | | | | 1002.4 TRAP SEALS. | | | EACH FIXTURE TRAP SHALL HAVE A LIQUID SEAL OF NOT LESS | | | THAN 2 INCHES (51 MM) AND NOT MORE THAN 4 INCHES (102 | | | MM), OR DEEPER FOR SPECIAL DESIGNS RELATING TO | | | ACCESSIBLE FIXTURES. WHERE A TRAP SEAL IS SUBJECT TO | | | LOSS BY EVAPORATION, A TRAP SEAL PRIMER VALVE SHALL BE | | | INSTALLED. TRAP SEAL PRIMER VALVES SHALL CONNECT TO THE | | | TRAP AT A POINT ABOVE THE LEVEL OF THE TRAP SEAL. A | | | TRAP SEAL PRIMER VALVE SHALL CONFORM TO ASSE 1018 OR | | | ASSE 1044. | | | | | | | | | TO SUBMIT A RREQUEST UNDER ALTERNANTE MATERIALS & | | | METHODS 104.11 IT HAS TO BE COMPLETED IN WRITTING TO | | | ROBERT BROWN THE WEST PALM BEACH BUILDING OFFICIAL FOR | | | REVIEW. | | | [email protected] | | | | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | | | | |
|