| Plan Review Notes For Permit 13080227 |
| Permit Number |
13080227 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-14 17:38:27 | 3111 45TH STREET - SUITE #17 | | | PERMIT #13080227 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHERS. EXTINGUISHERS | | | SHALL HAVE A MINIMUM RATING OF 2A:10BC AND SHALL BE | | | TAGGED BY A LICENSED FIRE EXTINGUISHER COMPANY. TRAVEL | | | DISTANCE TO EXTINGUISHERS SHALL NOT EXCEED 75 FEET. | | | | | | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH | | | EXIT SIGNS. | | | | | | PER NFPA 101 SECTION 7.2.1.4.3 DOOR LEAF ENCROACHMENT - | | | DURING ITS SWING, ANY DOOR LEAF IN A MEANS OF EGRESS | | | SHALL LEAVE NOT LESS THAN ONE-HALF OF THE REQUIRED | | | WIDTH OF AN AISLE, A CORRIDOR, A PASSAGEWAY, OR A | | | LANDING UNOBSTRUCTED AND SHALL PROJECT NOT MORE THAN | | | 7-INCHES INTO THE REQUIRED WIDTH OF AN AISLE, A | | | CORRIDOR, A PASSAGEWAY, OR A LANDING, WHEN FULLY OPEN. | | | | | | PER NFPA 101 SECTION 7.2.1.2.3.2, DOOR OPENINGS IN THE | | | MEANS OF EGRESS SHALL BE NOT LESS THAN 32-INCHES IN | | | CLEAR WIDTH. | | | | | | WESLEY JOLIN | | | FIRE INVESTIGATOR & INSPECTOR | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | [email protected] | | | (561) 805-6730 | | | |
|