| Plan Review Notes For Permit 13080209 |
| Permit Number |
13080209 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-06 14:19:54 | ADDITIONAL INFORMATION PROVIDED. ALLEQUIPMENT IS TO BE | | | LISTED FOR THE USE AND USED WITHIN THE LISTING. WIRE IN | | | WET LOCATIONS TO BE LISTED FOR THE LOCATION. | | | | | | | | | CALLED CONTRACTOR FOR MORE DETAILS. DID THEY CONSIDER | | | USING PVC FOR CORROSION PROTECTION? ALL EQUIPMENT AND | | | CABLES TO BE LISTD FOR THE USE. CABLES AND CONDUCTORS | | | UNDERGROUND OR IN CONCRETE TO BE WET LOCATION | | | LISTED.PLAN IS NOT CLEAR AS TO HOW POWER AND CONTROL | | | ARE BEING PROVIDED TO GATE ARMS. PROVIDE LISTING | | | INFORMATION AN CUT SHEETS ON EQUIPMENT. |
|