| Plan Review Notes For Permit 13080180 |
| Permit Number |
13080180 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-12 14:46:45 | 2007 FBC | | | | | | 1) SPECIFY THE REQUIRED COMPONENT AND CLADDING | | | PRESSURES FOR THE PROPOSED ROOF HATCH AND THE ROOF ZONE | | | IN WHICH IT WILL BE INSTALLED. THE PROJECT THAT THIS | | | REVISION REFERENCES WAS PERMITTED UNDER THE 2007 FBC | | | WITH THE 2009 SUPPLEMENTS. THEREFORE, THE WIND SPEED IS | | | 140 MPH EXPOSURE C AND THE MEAN ROOF HEIGHT IS 26' - | | | 6". 2007 FBC R301.2.1 | | | | | | 2) PLEASE SUBMIT TWO COPIES OF THE PRODUCT APPROVALS | | | FOR THE (BILCO) ROOF HATCH AS REQUIRED BY DCA RULE | | | 9B-72. | | | | | | 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED | | | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR | | | THE PROJECT. CITY AMENDMENTS 106.3.3 | | | | | | 4) SUBMIT TWO SIGNED AND SEALED SETS OF A REVISED ROOF | | | FRAMING PLAN, SHOWING THE FRAMED OPENING FOR THE ROOF | | | HATCH. PROVIDE ALL DETAILS INCLUDING CONNECTORS. CITY | | | AMENDMENTS 106.1.1 & 2007 FBC R801.2 | | | | | | NOTE: THE ROOF HATCH IS TO BE USED FOR MAINTENANCE | | | ACCESS TO ROOF ONLY. |
|