Plan Review Notes
Plan Review Notes For Permit 13080180
Permit Number 13080180
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-12 14:46:452007 FBC
  
 1) SPECIFY THE REQUIRED COMPONENT AND CLADDING
 PRESSURES FOR THE PROPOSED ROOF HATCH AND THE ROOF ZONE
 IN WHICH IT WILL BE INSTALLED. THE PROJECT THAT THIS
 REVISION REFERENCES WAS PERMITTED UNDER THE 2007 FBC
 WITH THE 2009 SUPPLEMENTS. THEREFORE, THE WIND SPEED IS
 140 MPH EXPOSURE C AND THE MEAN ROOF HEIGHT IS 26' -
 6". 2007 FBC R301.2.1
  
 2) PLEASE SUBMIT TWO COPIES OF THE PRODUCT APPROVALS
 FOR THE (BILCO) ROOF HATCH AS REQUIRED BY DCA RULE
 9B-72.
  
 3) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 106.3.3
  
 4) SUBMIT TWO SIGNED AND SEALED SETS OF A REVISED ROOF
 FRAMING PLAN, SHOWING THE FRAMED OPENING FOR THE ROOF
 HATCH. PROVIDE ALL DETAILS INCLUDING CONNECTORS. CITY
 AMENDMENTS 106.1.1 & 2007 FBC R801.2
  
 NOTE: THE ROOF HATCH IS TO BE USED FOR MAINTENANCE
 ACCESS TO ROOF ONLY.