| Plan Review Notes For Permit 13080168 |
| Permit Number |
13080168 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-03 16:48:18 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | FROM PREVIOUS LIST: | | | | | | 1. SEE FBC 1603.1.4, WIND DESIGN CRITERIA, WIND SPEED | | | IN BOTH VULT AND VASD TO BE PROVIDED. 150MPH WAS NOT | | | CLEAR; VULT OR VASD? MINIMUM FOR THIS LOCATION IS | | | 170MPH VULT / 132 VASD. PLEASE CLARIFY. | | | | | | ENGINEER MAY SEND A LETTER OF CLARIFICATION VIA EMAIL. | | | | | | 3RD REVIEW, WIND SPEEDCHANGED BUT EXPOSURE WAS CHANGED | | | FROM D TO B. PLEASE SEE THIS STRUCTURE ON AN AERIAL. IF | | | YOU BELIEVE THIS IS EXPOSURE B RATHER THAN D, PLEASE | | | CALL ME TO DISCUSS PRIOR TO RESUBMITTAL. OTHERWISE, | | | REVISE BACK TO EXPOSURE B. THIS STRUCTURE IS LOCATED ON | | | THE INTRACOASTAL. | | | | | | | | 2013-08-22 21:36:16 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2010 | | | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL | | | | | | 1. SEE FBC 1603.1.4, WIND DESIGN CRITERIA, WIND SPEED | | | IN BOTH VULT AND VASD TO BE PROVIDED. 150MPH WAS NOT | | | CLEAR; VULT OR VASD? MINIMUM FOR THIS LOCATION IS | | | 170MPH VULT / 132 VASD. PLEASE CLARIFY. | | | | | | ENGINEER MAY SEND A LETTER OF CLARIFICATION VIA EMAIL. | | | |
|