| 2013-08-09 13:23:19 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2010 |
| | FBC R FLORIDA BUILDING CODE 2010 RESIDENTIAL |
| | |
| | |
| | 1. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE |
| | ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER |
| | FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED. |
| | THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET |
| | AT |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_ |
| | INSTALLATION.PDF |
| | |
| | THIS IS A REPEAT COMMENT FOR THIS CONTRACTOR. PLEASE |
| | INCLUDE IN ALL SHUTTER PERMIT APPLICATIONS. IF |
| | APPLICATIONS CONTINUE TO BE SUBMITTED WITHOUT THE |
| | REQUIRED INFORMATION, PERMITS WILL BE ISSUED WITH |
| | PROVISO THAT THE INFORMATION BE PROVIDED AS A REVISION. |
| | |
| | 2. PROVIDE A LIFE SAFETY PLAN. THIS IS A COMMERCIAL |
| | BUILDING AND THERE IS NO PROVISION FOR BLOCKING OF |
| | REQUIRED EXITS: |
| | |
| | FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF |
| | EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE |
| | INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS |
| | OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER. |
| | OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH |
| | OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY |
| | THIS CHAPTER. |
| | |
| | LIFE SAFETY PLAN SHOULD SHOW ALL EXITS, EXIT SIGNS, |
| | TRAVEL DISTANCE, EXIT TO BE COVERED WITH THE SHUTTER, |
| | ALTERNATE EXITS. |
| | |