| Plan Review Notes For Permit 13080164 |
| Permit Number |
13080164 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-08 07:09:58 | PLAN SHOWS A 100 SWITCH WITH A 125A PANEL. PAPERWORK | | | STATES A NEMA 1 ENCLOSURE AND LOCATION OF TRANSFER | | | SWITCH IS NOT CLEAR. PROVIDE OVERCURRENT PROTECTION | | | LOCATIONS AND SIZES TO DEFINE THE EDGES OF THE SERVICE. | | | BONDING AND GROUNDING TO COMPLY WITH NEC 250 FOR | | | SERVICE RACEWAYS AND FEEDERS. DOES THE GENERATOR HAVE A | | | MAIN BREAKER? WHAT SIZE? WHAT IS THE AIC AVAIALBLE AND | | | WHAT IS THE RATING OF THE EQUIPMENT TO BE INSTALLED? | | | DOES THE INSTALLATION PROVIDE SUFFICIENT WORKING | | | CLEARANCE PER NEC 110.16? INDICATE WHICH APPLIANCES ARE | | | GAS AND WHICH ARE ELECTRIC. INDICATE WHAT APPLIANCES, | | | IF ANY, ARE CONNECTED TO LOAD SHEDDING AND PROVIDE | | | DETAILED LOAD CALCULATION FOR "NORMAL" AND "EMERGENCY" | | | OPERATION. PAPERWORK INDICATES "SELECTED LIGHTING | | | CIRCUITS" AND A SECOND PANEL IS NOT SHOWN. SHOW TYPE OF | | | FUEL SUPPLY AND LOCATION TO FEED GENERATOR. PERMIT | | | REQUIRED FOR INSTALLATION OF FUEL SUPPLY TO GENERATOR. | | | ADDITIONAL COMMENTS MAY RESULT FROM SUBMISSION OF THE | | | REQUIRED PAPERWORK. |
|