| Plan Review Notes For Permit 13080143 |
| Permit Number |
13080143 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-05 17:09:52 | WIND LOAD WAS PERFORMED WITHOUT FIXTURES. PROVIDE | | | REVISED ENGINEERED WIND LOAD SHOWING THE FIXTURE AND | | | ARMS IN PLACE. PLANS AND ENGINEERING DO NOT AGREE FOR | | | POLE INSETION DEPTH. | | | PROVIDE CLEAR PHOTOMETRICS OF DESIGN TO ENSURE SAFETY | | | AND LIGHTING BEYOND THE PROPERTY LINE DOES NOT EXCEED | | | .5 FC AND HOW IT WILL BE ACHIEVED IN ACCORDANCE WITH | | | THE LISTING OF THE FIXTURE. CLEARLY IDENTIFY POLE | | | LOCATIONS AND FIXTURE CONFIGURATION ON PHOTOMETRIC | | | PLAN. | | | PROVIDE LISTING INFORMATION FOR FIXTURES AND ALL | | | COMPONENTS | | | PROVIDE VOLTAGE DROP CALCS SHOWING COMPLIANCE WITH | | | FBC-EC 505.7.3 | | | PROVIDE EXTERIOR LIGHTING POWER DENSITY INFORMATION PER | | | FBC-EC 505.6 | | | PROVIDE TIME CLOCK WITH PROGRAMING BACKUP FOR MINIMUM | | | 10 HOURS PER FBC-EC 505.2.4 | | | |
|