| Notes |
| Date |
Text |
| 2013-08-05 16:36:54 | APPROVED WITH THE FOLLOWING NOTES: | | | UNDERGROUND CABLES TO BE LISTED FOR USE IN WET | | | LOCATIONS | | | ALL EQUIPMENT TO BE LISTED AND USED WITHIN THE LISTING | | | FOR THE SPECIFIC ITEM | | | PROVIDE AND ENGINEERED AND SEALED WINDLOAD ANALYSIS AND | | | CALCULATIONS FOR THE POLES AND EQUIPMENT AT THE TIME OF | | | THE FIRST INSPECTION FOR CITY FILE | | | FIBER OPTIC TO BE CONNECTED PER NEC 770; SPECIFICALLY | | | 770.24, 770.93 AND 770.101 | | | PROVIDE SEPARATION OF LINE AND LOW VOLTAGE IN THE | | | GROUND, IN THE POLE AND AT POINT OF USE 110, 725, 770, | | | 800 | | | |
|