| Date |
Text |
| 2013-08-17 09:00:29 | MECHANICAL PLAN REVIEW |
| | PERMIT: 13080113 |
| | ADD: 319 CLEMATIS ST # 510 |
| | CONT: CLAY KOHLMEYER |
| | TEL: (561)694-1214 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: SATURDAY AUGUST 17/2013 |
| | ACTION: PROVISO |
| | |
| | 1) 48X12 EXISTING TRUNK LINE, LEFT TENANT SEPERATION |
| | WALL MISSING FIRE DAMPER PER 2010 FBC-M 607.5.3.607.5.3 |
| | FIRE PARTITIONS. |
| | DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATE FIRE |
| | PARTITIONS SHALL BE PROTECTED WITH LISTED FIRE DAMPERS |
| | INSTALLED IN ACCORDANCE WITH THEIR LISTING. |
| | |
| | 2) PLANS INDICATE THIS IS A PLENUM STYLE RETURN, PLANS |
| | FAIL TOINDICATE WHERE THE RETURN AIR TRANSFER OPENINGS |
| | AND FIRE DAMPERS ARE IN THE FIRE RATED TENANT |
| | SEPERATION WALL. 2010 FBC-M 607.5.3.607.5.3 FIRE |
| | PARTITIONS. THE DESIGNER OF RECORD IS ELECTING TO USE 1 |
| | HR TENANT SEPERATION WALLS. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |