Plan Review Notes
Plan Review Notes For Permit 13080113
Permit Number 13080113
Review Stop M
Sequence Number 1
Notes
Date Text
2013-08-17 09:00:29MECHANICAL PLAN REVIEW
 PERMIT: 13080113
 ADD: 319 CLEMATIS ST # 510
 CONT: CLAY KOHLMEYER
 TEL: (561)694-1214
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SATURDAY AUGUST 17/2013
 ACTION: PROVISO
  
 1) 48X12 EXISTING TRUNK LINE, LEFT TENANT SEPERATION
 WALL MISSING FIRE DAMPER PER 2010 FBC-M 607.5.3.607.5.3
 FIRE PARTITIONS.
 DUCTS AND AIR TRANSFER OPENINGS THAT PENETRATE FIRE
 PARTITIONS SHALL BE PROTECTED WITH LISTED FIRE DAMPERS
 INSTALLED IN ACCORDANCE WITH THEIR LISTING.
  
 2) PLANS INDICATE THIS IS A PLENUM STYLE RETURN, PLANS
 FAIL TOINDICATE WHERE THE RETURN AIR TRANSFER OPENINGS
 AND FIRE DAMPERS ARE IN THE FIRE RATED TENANT
 SEPERATION WALL. 2010 FBC-M 607.5.3.607.5.3 FIRE
 PARTITIONS. THE DESIGNER OF RECORD IS ELECTING TO USE 1
 HR TENANT SEPERATION WALLS.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]