| Plan Review Notes For Permit 13080083 |
| Permit Number |
13080083 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2013-09-09 06:53:15 | MIKE WITH HURRICANE PROVIDED REVISIONS SUITABLE FOR | | | ISSUANCE. PLANS RE-REVIEWED AND SIGNED OFF. DH 9/10/13 | | | | | | | | | | | | LOAD CALULATION AND RISER DO NOT AGREE - ONE SHOWS 400A | | | AND ONE SHOWS 200A | | | PROVIDE INTERSYSTEM BONDING POINT PER 250.94 | | | PROVIDE 3 WAY SWITCH AT STEPS | | | NO CLOSETS ARE SHOWN IN THE BEDROOMS. PLEASE LOCATE | | | SMOKE ALARMS IN ACCORDANCE WITH MANUFACTURERS | | | SPECIFICATIONS FOR BEST COVERAGE AND EARLIEST DETECTION | | | PROVIDE CALCULATION SHOWING 22K AIC GEAR AND CLARIFY | | | RATING OF THE METER CAN. WHAT IS DOWNSTREAM LETTHROUGH? | | | |
|