| Plan Review Notes For Permit 13080083 |
| Permit Number |
13080083 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-08-28 09:43:03 | BUILDING REVIEW APPROVED WITH PROVISO (PROVIDE | | | INFORMATION PRIOR TO INSPECTION TO AVOID CONFLICTS OR | | | DELAYS): | | | | | | 1- PROVIDE PRODUCT APPROVALS FOR: | | | A) SHINGLES. NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY | | | MIAMI-DADE. | | | | | | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON | | | PLANS. | | | | | | 2- ENGINEER OF RECORD TO REVIEW ALL PRODUCT APPROVALS. | | | | | | 3- A) REVISE TENANT SEPARATION WALL SECTION. NEED | | | TENANT SEPARATION AT FLOOR CEILING AREA. NEED TO | | | SPECIFY ASSEMBLY TESTED PER ASTM E 119 OR UL 263 AS | | | REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. AND, | | | COORDINATE THIS INFORMATION WITH THE EXISTING TYPICAL | | | WALL SECTION SUBMITTED. | | | ***NOTE; ASSEMBLY TO INCLUDE INSULATION AS SHOWN ON | | | PLANS.. | | | | | | B) PROVIDE SPECIFICATIONS FOR THE FIRE RATING OF THE | | | SUPPORTING CONSTRUCTION AS REQUIRED BY SEC. R302.3.1. | | | | | | C) PROVIDE SPECIFICATIONS FOR THE RATED PENETRATIONS AS | | | REQUIRED BY SEC. R302.4. |
|