Plan Review Notes
Plan Review Notes For Permit 13080083
Permit Number 13080083
Review Stop B
Sequence Number 1
Notes
Date Text
2013-08-07 17:41:46RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- CLARIFY SCOPE OF WORK. PLANS SUBMITTED DON'T SPECIFY
 SHINGLES RE-ROOF BUT THERE WERE SHINGLES AND
 UNDERLAYMENT PRODUCT APPROVALS SUBMITTED. REVISE AS
 REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  
 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY
 DCA RULE 9N-3 FOR:
 A) SHINGLES (IF DOING RE-ROOF. SEE COMMENT #1 ABOVE.).
 NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE.
 NEED CURRENT NOA.
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 PLANS.
  
 C) WINDOW MULLIONS AS SHOWN ON PLANS.
  
 3- ENGINEER OF RECORD TO REVIEW PRODUCT APPROVALS. SEC.
 107.3.4.1 CITY AMENDMENTS.
  
 4- A) REVISE TENANT SEPARATION WALL SECTION. NEED
 TENANT SEPARATION AT FLOOR CEILING AREA. NEED TO
 SPECIFY ASSEMBLY TESTED PER ASTM E 119 OR UL 263 AS
 REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. AND,
 COORDINATE THIS INFORMATION WITH THE EXISTING TYPICAL
 WALL SECTION SUBMITTED.
 ***NOTE: ASSEMBLY TO INCLUDE INSULATION AS SHOWN ON
 PLANS.
  
 B) PROVIDE SPECIFICATIONS FOR THE FIRE RATING OF THE
 SUPPORTING CONSTRUCTION AS REQUIRED BY SEC. R302.3.1.
  
 C) PROVIDE SPECIFICATIONS FOR THE RATED PENETRATIONS AS
 REQUIRED BY SEC. R302.4.
  
 5- BEDROOM WINDOWS: CLEARLY IDENTIFY ON PLANS TYPE AND
 SIZE OF EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE
 EGRESS REQUIREMENTS OF SEC. 601.2 OF 2010 FBC-EXISTING
 BUILDING.
  
 6- SPECIFY HOW PROVIDING HEAT AS REQUIRED BY SEC.
 R303.8.
  
 7- PROVIDE ENERGY CALCULATIONS. SEC. 103.2 OF 2010
 FBC-ENERGY CONSERVATION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712