| 2013-08-07 17:41:46 | RESIDENTIAL (R3) RENOVATION, BUILDING REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- CLARIFY SCOPE OF WORK. PLANS SUBMITTED DON'T SPECIFY |
| | SHINGLES RE-ROOF BUT THERE WERE SHINGLES AND |
| | UNDERLAYMENT PRODUCT APPROVALS SUBMITTED. REVISE AS |
| | REQUIRED. SEC. 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) SHINGLES (IF DOING RE-ROOF. SEE COMMENT #1 ABOVE.). |
| | NOA 11-1122.04 SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| | NEED CURRENT NOA. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS. |
| | |
| | C) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW PRODUCT APPROVALS. SEC. |
| | 107.3.4.1 CITY AMENDMENTS. |
| | |
| | 4- A) REVISE TENANT SEPARATION WALL SECTION. NEED |
| | TENANT SEPARATION AT FLOOR CEILING AREA. NEED TO |
| | SPECIFY ASSEMBLY TESTED PER ASTM E 119 OR UL 263 AS |
| | REQUIRED BY SEC. R302.3 OF 2010 FBC-RESIDENTIAL. AND, |
| | COORDINATE THIS INFORMATION WITH THE EXISTING TYPICAL |
| | WALL SECTION SUBMITTED. |
| | ***NOTE: ASSEMBLY TO INCLUDE INSULATION AS SHOWN ON |
| | PLANS. |
| | |
| | B) PROVIDE SPECIFICATIONS FOR THE FIRE RATING OF THE |
| | SUPPORTING CONSTRUCTION AS REQUIRED BY SEC. R302.3.1. |
| | |
| | C) PROVIDE SPECIFICATIONS FOR THE RATED PENETRATIONS AS |
| | REQUIRED BY SEC. R302.4. |
| | |
| | 5- BEDROOM WINDOWS: CLEARLY IDENTIFY ON PLANS TYPE AND |
| | SIZE OF EXISTING WINDOWS TO VERIFY COMPLIANCE WITH THE |
| | EGRESS REQUIREMENTS OF SEC. 601.2 OF 2010 FBC-EXISTING |
| | BUILDING. |
| | |
| | 6- SPECIFY HOW PROVIDING HEAT AS REQUIRED BY SEC. |
| | R303.8. |
| | |
| | 7- PROVIDE ENERGY CALCULATIONS. SEC. 103.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |