| 2013-08-27 18:40:39 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND BUILDING |
| | REVIEW COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS. SEC. 103.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. (NO ADDRESSED). |
| | ***AND COORDINATE WITH FLOOR PLANS. |
| | |
| | 2- PROVIDE COMPLETE WINDOW/DOOR FRAMING DETAILS. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | ***HEADER FRAMING DETAIL IS MISSING STUDS. DETAIL ON |
| | SHEET NO 2 IS ONLY SHOWING ONE STUD SUPPORTING THE |
| | HEADER. REVISE AS REQUIRED. |
| | |
| | 3- SHEET #2: |
| | A) REVISE ALL ROOF SHEATHING NAILING SPECIFICATIONS. |
| | NEED TO USE 8D RING SHANK NAILS MIN. (ALL OTHER NAILS |
| | SPECIFIED ON PLYWOOD NAILING REQUIREMENTS ARE NOT |
| | ALLOWED). AND ROOF ZONE #3 NAIL SPACING IS 4"O.C. SEE |
| | SEC. R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) ROOF DIAGRAM IS MISSING ROOF ZONE #3 ON THE HIP |
| | ROOF. SEE FIGURE R301.2(7) AND REVISE AS REQUIRED. |
| | |
| | 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF SHINGLES. NOA 11-1122.04 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| | (NOT ADDRESSED). |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS, SECTIONS, DETAILS. (NOT ADDRESSED). |
| | |
| | 5- ENGINEER OF RECORD TO REVIEW AND APPROVED ABOVE |
| | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH ITEM |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | |