| Plan Review Notes For Permit 13080082 |
| Permit Number |
13080082 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-13 07:17:33 | 2010 FBC / 2008 NEC | | | | | | DENIED BY ELECTRICAL | | | | | | 1) SHOW THE LOCATION OF THE METER CAN AND SERVICE | | | DISCONNECT ON THE PLANS. NEC 230.70 | | | | | | 2) SHOW THE LOCATION OF THE PANELBOARD ON THE PLANS. | | | NEC 240.24 | | | | | | 3) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) WHICH | | | REQUIRES AT LEAST ONE RECEPTACLE AT THE FRONT AND REAR | | | OF THE DWELLING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|