Plan Review Notes
Plan Review Notes For Permit 13080082
Permit Number 13080082
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-13 07:17:332010 FBC / 2008 NEC
  
 DENIED BY ELECTRICAL
  
 1) SHOW THE LOCATION OF THE METER CAN AND SERVICE
 DISCONNECT ON THE PLANS. NEC 230.70
  
 2) SHOW THE LOCATION OF THE PANELBOARD ON THE PLANS.
 NEC 240.24
  
 3) SHOW COMPLIANCE WITH NEC 210.52 (E) (1) WHICH
 REQUIRES AT LEAST ONE RECEPTACLE AT THE FRONT AND REAR
 OF THE DWELLING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW