| 2013-08-05 19:01:01 | RESIDENTIAL (R3) ADDITION/RENOVATION BUILDING REVIEW |
| | COMMENTS. |
| | CODE: 2010 FBC. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY TO VERIFY IF IMPACT FEES ARE DUE. BRING BACK |
| | COUNTY STAMPED PLANS AND COPY OF PAID RECEIPT IF FEES |
| | ARE DUE. REQUIRED BY THE COUNTY IMPACT FEE ORDINANCE OF |
| | THE UNIFIED LAND DEVELOPMENT CODE. |
| | |
| | 2- SPECIFY SIZE OF ENTRY DOOR TO VERIFY COMPLIANCE WITH |
| | SEC. R311 OF 2010 FBC-RESIDENTIAL. |
| | |
| | 4- PROVIDE COMPLETE WALL SECTION FOR NEW CONSTRUCTION |
| | (SEC. 107.3.5.3(5) CITY AMENDMENTS) SPECIFYING: |
| | A) ALL CONNECTORS (TOP/BOTTOM). |
| | |
| | B) STUCCO THICKNESS. |
| | |
| | C), 2 LAYERS OF VAPOR BARRIER, |
| | |
| | D) CLEARANCE FROM FINISHED GRADE, |
| | |
| | E) ATTIC VENTILATION, SIZE AND SPACING. |
| | |
| | 5- NOTE: WALL SECTION PROVIDED IS FOR THE EXISTING |
| | WALLS AND IS MISSING ALL THIS INFORMATION ALSO. |
| | |
| | 6- PROVIDE ENERGY CALCULATIONS. SEC. 103.2 OF 2010 |
| | FBC-ENERGY CONSERVATION. |
| | ***COORDINATE WITH FLOOR PLANS. |
| | |
| | 7- THIS DWELLING UNIT DOESN'T PROVIDE A LEAST ONE ROOM |
| | WITH 120 S.F. AS REQUIRED BY SEC. R304.1 OF 2010 |
| | FBC-RESIDENTIAL. REVISE AS REQUIRED. |
| | |
| | 8- SPECIFY HOW PROVIDING HEAT AS REQUIRED BY SEC. |
| | R303.8 OF 2010 FBC-RESIDENTIAL. |
| | ***NOTE: PORTABLE WALL UNIT IS NOT ALLOWED. |
| | |
| | 9- PROVIDE COMPLETE WINDOW/DOOR FRAMING DETAILS. SEC. |
| | 107.2.1 CITY AMENDMENTS TO FBC. |
| | |
| | 10- PROVIDE COMPLETE GABLE END CONSTRUCTION DETAIL TO |
| | SHOW HOW ARE THE LOADS TRANSFERED AS REQUIRED BY SEC. |
| | R601.2 OF 2010 FBC-RESIDENTIAL. SPECIFY ALL CONNECTORS. |
| | |
| | 11- SHEET #2: |
| | A) ROOF SHEATHING NAILING NOTE IS MISSING ROOF ZONE #3. |
| | SPECIFY NAILING FOR ROOF ZONE #3 AS REQUIRED BY SEC. |
| | R803.2.3.1 OF 2010 FBC-RESIDENTIAL. |
| | |
| | B) ZONE #3 IS 5'-0" MIN. AS REQUIRED BY FIGURE |
| | R803.2.3.1 OF 2010 FBC-RESIDENTIAL. IDENTIFY ROOF ZONE |
| | #3 ON ROOF FRAMING PLAN. |
| | |
| | 12- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) ROOF SHINGLES. NOA 11-1122.04 SUBMITTED WAS |
| | SUPERSEDED BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. |
| | |
| | B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON |
| | PLANS, SECTIONS, DETAILS. |
| | |
| | 13- ENGINEER OF RECORD TO REVIEW AND APPROVED ABOVE |
| | PRODUCT APPROVALS. SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | ***PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH ITEM |
| | TO EXPEDITE THE REVIEW PROCESS. |
| | |