2013-08-20 17:36:27RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- REVISE PLUMBING RISER DIAGRAM. NOT MORE THAN ONE
 FIXTURE SHALL DISCHARGE UPSTREAM OF THE DRY VENT. SEE
 SEC. P3108.2.1 OF 2010 FBC-RESIDENTIAL.
  
 2- SANITARY RISER DIAGRAM SUBMITTED:
 A) CLEANOUT REQUIRED. SEC. P3005.2
 B) THERE IS NO ABBREVIATION LEGEND. CLARIFY WHAT'S
 "CTG". SEC. 107.2.1 CITY AMENDMENTS TO FBC.
  