| Plan Review Notes For Permit 13071177 |
| Permit Number |
13071177 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-20 17:36:27 | RESIDENTIAL (R3) ADDITION, PLUMBING REVIEW COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- REVISE PLUMBING RISER DIAGRAM. NOT MORE THAN ONE | | | FIXTURE SHALL DISCHARGE UPSTREAM OF THE DRY VENT. SEE | | | SEC. P3108.2.1 OF 2010 FBC-RESIDENTIAL. | | | | | | 2- SANITARY RISER DIAGRAM SUBMITTED: | | | A) CLEANOUT REQUIRED. SEC. P3005.2 | | | B) THERE IS NO ABBREVIATION LEGEND. CLARIFY WHAT'S | | | "CTG". SEC. 107.2.1 CITY AMENDMENTS TO FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|