2013-08-20 17:30:56RESIDENTIAL (R3) ADDITION, MECHANICAL REVIEW COMMENTS.
 CODE: 2010 FBC.
  
 1- PROVIDE EQUIPMENT SIZING CALCULATIONS SHOWING
 EQUIPMENT LISTED IN THE A/C PLAN SUBMITTED. SEC. 403.6
 OF 2010 FBC-ENERGY CONSERVATION.
  