| 2013-10-28 12:00:24 | THIRD BUILDING REVIEW COMMENTS. |
| | |
| | 1- TITLE BLOCK FOR SHEETS P-01 AND E-01 HAVE THE NAME |
| | OF THE ENGINEER JOHN H. CRESWELL AND THE ARCHITECTS' |
| | OFFICE "SSC DESIGN GROUP". ACCORDING TO FLORIDA |
| | STATUTES 471 AND 481 ALL SHEETS WITH AN ENGINEER OR |
| | ARCHITECT NAME MUST BE SIGNED AND SEALED BY THE |
| | LICENSED PROFESSIONAL. OTHERWISE, REMOVE THE NAMES FROM |
| | THE TITLE BLOCK AND PROVIDE ONLY THE NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR THE DESIGN. SEC. 107.2.1 |
| | CITY AMENDMENTS TO FBC. |
| | |
| | 2- REVISE DETAIL 3 ON SHEET A1. CONCRETE BLOCK WALL |
| | INSULATION R-VALUE TO MATCH THE ONE REQUIRED BY THE |
| | ENERGY CALCULATIONS. SEC. 103.2.2 OF 2010 FBC-ENERGY |
| | CONSERVATION. |
| | |
| | 3- ENERGY CALCULATIONS SUBMITTED ARE TAKING THE CEILING |
| | FAN CREDIT. SPECIFY ON PLANS CEILING FAN SIZE FOR ALL |
| | ROOMS AS REQUIRED BY SEC. 405.6.6 OF 2010 FBC-ENERGY |
| | CONSERVATION AND TABLE 405.6.6. (***NOTE: CALCULATIONS |
| | ARE DONE FOR THE ENTIRE HOUSE, THEREFORE IF TAKING |
| | CEILING FAN CREDIT, THEN ALL THE ROOMS NEED TO HAVE |
| | CEILING FANS). |
| | |
| | 4- PROVIDE COMPLETE INSTALLATION SCHEDULE FOR THE |
| | INSTALLATION OF SHUTTERS. NEED THIS INSTALLATION |
| | SCHEDULE TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES |
| | OF PRODUCT APPROVAL PROPOSED INSTALLATION AND THE |
| | DESIGN PRESSURES REQUIRED BY SEC. R301.2.1.4.3. (REPEAT |
| | COMMENT) |
| | |
| | |
| | ***NOTE: PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO EXPEDITE THE REVIEW PROCESS. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |