| Plan Review Notes For Permit 13071145 |
| Permit Number |
13071145 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2013-09-20 08:32:21 | RESIDENTIAL (R3) ADDITION/ALTERATION, SECOND MECHANICAL | | | REVIEW CHECKLIST. | | | CODE: 2010 FBC. | | | | | | 1- THERE WAS NO A/C INFORMATION SUBMITTED THE FIRST | | | TIME, EXCEPT FOR THE 5" FLEX DUCT SHOWN ON SHEET A-06 | | | TO FEED THE NEW CABANA. CLARIFY SCOPE OF WORK. NOW, | | | THERE ARE EQUIPMENT SIZING CALCULATIONS SUBMITTED. WHY | | | SUBMITTING THESE CALCULATIONS. IS THERE GOING TO BE AN | | | EXACT CHANGE OUT. IF SO, PROVIDE COMPLETE EQUIPMENT | | | SIZING CALCULATIONS, NOT JUST THE SUMMARY AND COMPLETE | | | THE REQUIRED CHANGE OUT FORMS. IF DOING ANY OTHER | | | DUCTWORK, THEN A/C PLANS ARE REQUIRED. SEC. | | | 107..5.3(10) OF CITY AMENDMENTS TO FBC. | | | | | | 2- PROVIDE SPECIFICATIONS FOR EXHAUST HOOD TO BE | | | INSTALLED ABOVE THE GRILL IN THE SUMMER KITCHEN. AND, | | | CLARIFY WHERE I S THE HOOD VENTING TO. ELEVATIONS DON'T | | | SHOW HOOD VENTING TO THE ROOF. SEC. M1505 OF 2010 | | | FBC-RESIDENTIAL (REPEAT COMMENT). | | | | | | 3- SPECIFY THE EXHAUST FAN FOR BATHROOM #1 AS REQUIRED | | | BY SEC. M1507. ONLY SHOWING EXHAUST FAN AT THE TOILET | | | ROOM (REPEAT COMMENT). | | | | | | | | | ****NOTE; PLEASE PROVIDE RESPONSE LETTER ADDRESSING | | | EACH COMMENT TO EXPEDITE THE REVIEW PROCESS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6712 |
|