| 2013-08-26 18:48:35 | RESIDENTIAL (R3) ADDITION/ALTERATION, MECHANICAL REVIEW | | | COMMENTS. | | | CODE: 2010 FBC. | | | | | | 1- PROVIDE SPECIFICATIONS FOR EXHAUST HOOD TO BE | | | INSTALLED ABOVE THE GRILL IN THE SUMMER KITCHEN. AND, | | | CLARIFY WHERE I S THE HOOD VENTING TO. ELEVATIONS DON'T | | | SHOW HOOD VENTING TO THE ROOF. SEC. M1505 OF 2010 | | | FBC-RESIDENTIAL. | | | | | | 2- SPECIFY THE EXHAUST FAN FOR BATHROOM #1 AS REQUIRED | | | BY SEC. M1507. ONLY SHOWING EXHAUST FAN AT THE TOILET | | | ROOM. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6712 | | 2013-08-23 12:22:43 | REVIEW IN PROGRESS... |
|