| Plan Review Notes For Permit 13071125 |
| Permit Number |
13071125 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2013-08-01 07:44:18 | 2010 FBC | | | 170 MPH EXPOSURE B | | | | | | DENIED BY BUILDING | | | | | | 1) SUBMIT TWO COPIES OF THE PRODUCT APPROVAL FOR THE | | | ROOF TILE AND SPECIFY THE TYPE OF ATTACHMENT ATTACHMENT | | | THAT WILL BE USED TO INSTALL IT. IF AN ADHESIVE IS USED | | | SUBMIT TWO COPIES OF THE PRODUCT APPROVALS FOR IT. DCA | | | RULE 9N-3 AND FBC R301.2.1 | | | | | | 2) SUBMIT TWO COPIES OF A DIMENSIONED DIAGRAM OF THE | | | ROOF SHOWING THE AREAS WHERE THE REPAIRS ARE BEING | | | MADE. FBC EXISTING BUILDING 611.1.1 NOT MORE THAN 25 | | | PERCENT OF ROOF AREA CAN BE REPAIRED UNLESS THE ENTIRE | | | ROOF SYSTEM CONFORMS WITH THIS CODE. | | | | | | 3) THERE IS A CODE VIOLATION ON RECORD FOR ROOFING AND | | | STRUCTURAL REPAIRS THAT WERE PREFORMED WITHOUT THE | | | PROPER PERMITS. A PENALTY FEE WILL BE ADDED TO THE | | | REQUIRED PERMIT FEE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|