| 2013-08-19 14:03:50 | BUILDING PLAN REVIEW |
| | REVISION: 13071115 |
| | PERMIT: 13010504 |
| | ADD: 631 EVERNIA ST |
| | CONT: KAUFMAN LYNN |
| | TEL: (561)361-6700 |
| | 2010 FLORIDA BUILDING CODE W |
| | * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS |
| | 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013. |
| | |
| | 2010 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | DATE: AUGUST 19/ 2013 |
| | ACTION: DENIED |
| | |
| | 1) SHEET A0450 INDICATES A REVISION FROM THE USE OF |
| | METAL ROOF TILE TO CONCRETE ROOF TILE. IN THE |
| | SUPPORTING DOCUMENTS, THERE IS NO PRODUCT TESTING |
| | SHOWING COMPLIANCE WITH: |
| | 2010 FBC 2010 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| | 1609.6.4.41 COMPONENTS & CLADDING |
| | |
| | FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV. |
| | 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION |
| | SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS: |
| | (31)(D) ROOFING PRODUCTS AND ASSEMBLIES, PLEASE |
| | IDENTIFY THE TILE TYPE, AND THE ANCHOR METHOD. ALSO IF |
| | FOAM PRODUCTS ARE BEING USED FOR ANCHORING PLEASE |
| | REVIEW 2010 FBC-B 603.4, TABLE 1505.1 & 1505.3. |
| | |
| | 2) SHEETS A500 SERIES AND A600 SERIES INDICATE THE USE |
| | OF FIBERTECH FRP MOLDINGS, FC-2261, PLEASE PROVIDE |
| | COMPLIANCE WITH 2010 FBC-B |
| | 1406.2.2 TYPE I, II, III AND IV CONSTRUCTION.2. |
| | COMBUSTIBLE ARCHITECTURAL TRIM SHALL BE LIMITED TO 40 |
| | FEET (12 192 MM) IN HEIGHT ABOVE GRADE. |
| | |
| | PLEASE PROVIDE PRODUCT TESTING THAT MEETS THE |
| | DEFINITION OF NONCOMBUSTIBILITY AND TEST 703.4. PLEASE |
| | REVIEW: |
| | |
| | 703.4.1 ELEMENTARY MATERIALS. |
| | MATERIALS REQUIRED TO BE NONCOMBUSTIBLE SHALL BE TESTED |
| | IN ACCORDANCE WITH ASTM E 136. |
| | |
| | 703.4.2 COMPOSITE MATERIALS. |
| | MATERIALS HAVING A STRUCTURAL BASE OF NONCOMBUSTIBLE |
| | MATERIAL AS DETERMINED IN ACCORDANCE WITH SECTION |
| | 703.4.1 WITH A SURFACING NOT MORE THAN 0.125 INCH (3.18 |
| | MM) THICK THAT HAS A FLAME SPREAD INDEX NOT GREATER |
| | THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84 OR UL |
| | 723 SHALL BE ACCEPTABLE AS NONCOMBUSTIBLE MATERIALS. |
| | |