Plan Review Notes
Plan Review Notes For Permit 13071105
Permit Number 13071105
Review Stop B
Sequence Number 1
Notes
Date Text
2013-07-31 13:49:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724
 [email protected]
  
 PER WPB ADMIN CODE 94-546(B):
  
 1. THIS PARCEL IS LOCATED IN A SPECIAL HAZARD FLOOD
 ZONE. IT APPEARS THAT THIS IS A SUBSTANTIAL
 IMPROVEMENT. IF THIS IS A SUBSTANTIAL IMPROVEMENT, THE
 STRUCTURE AND ASSOCIATED EQUIPMENT ARE TO BE BROUGHT
 INTO COMPLIANCE. A SUBSTANTIAL IMPROVEMENT OCCURS WHEN
 CUMULATIVE LIFETIME IMPROVEMENTS EXCEED 50% OF THE
 VALUE OF THE STRUCTURE.
  
 AN ELEVATION CERTIFICATE IS ON FILE WHICH SHOWS A
 STRUCTURE IN COMPLIANCE AT 7.5' FFE, BUT MECHANICAL
 EQUIPMENT AT 7'. RAISING THE MECHANICAL EQUIPMENT AND
 PROVIDING AN UPDATED ELEVATION CERTIFICATE IS AN OPTION
 FOR COMPLIANCE (IF THE ELEVATION CERTIFICATE IS FOR THE
 SAME STRUCTURE AS THE PROPOSED WORK).
  
 OTHER OPTIONS:
  
 IDENTIFY THE CUMULATIVE LIFETIME IMPROVEMENTS AT THIS
 ADDRESS TO PROVIDE EVIDENCE THAT THIS STRUCTURE HAS NOT
 EXCEEDED 50% IMPROVEMENTS.
  
 PROVIDE A CERTIFIED APPRAISAL OR PROPERTY APPRAISER
 DATA WHICH PROVIDES VALUE FOR THIS STRUCTURE.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU NEED FURTHER
 ASSISTANCE.
  
  