Plan Review Notes
Plan Review Notes For Permit 13071103
Permit Number 13071103
Review Stop E
Sequence Number 1
Notes
Date Text
2013-08-15 16:08:46WHOLE BUILDING ENERGY CODE REPORT REQUIRED PER FBC-EC
 101.4.9
 NOTE ON FRONT PAGE STATE "2010 NATIONAL ELECTRIC CODE,
 NFPA" AND NO SUCH DOCUMENT EXISTS
 PROVIDE LISTING INFORMATION ON SUSPENDED CEILING IF
 USED FOR SUPPORT OF FIXTURES 110.3, 410.36 (B)
 LIGHTING LOADS ON LOAD CALCS DO NOT APPEAR TO AGREE
 WITH THE ENERGY CALCULATION PROVIDED?
 NO FIRE ALARM SHOWN, ASSUMED TO BE PERMITTED SEPARATELY
 ENSURE STROBES ARE VISIBLE IN DRESSING ROOMS
 SEPARATE PERMITS REQUIRED FOR: VIDEO, AUDIO, ALARM,
 PHONE, DATA AND/OR OTHER SYSTEMS.