Plan Review Notes
Plan Review Notes For Permit 13071098
Permit Number 13071098
Review Stop B
Sequence Number 3
Notes
Date Text
2014-01-02 10:20:36BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 3RD REVIEW
 DATE: THURSDAY 01/02/2014
 ACTION: BUILDING PROVISO:
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
  
  
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH
  
  
 BUILDING PROVISO:
 MIAMI-DADE PRODUCT APPROVAL: 11-0722.10 ROOF HATCH +/-
 70 PSF PLEASE REVIEW SHEET A-141, TENANT B-12 THIS ROOF
 HATCH IS IN ROOF ZONE # 2 WITH ASSOCIATED PRESSURES OF
 -76.5 IN EXCESS OF THE PRODUCT APPROVAL, THE ROOF HATCH
 NEEDS TO BE MOVED INTO ROOF ZONE # 1 FOR THE ROOF TOP
 PRESSURES TO BE LOWER THAN THE LIMITS IN THE PRODUCT
 APPROVAL. TENANTS B13, B14 & B15 OK.
  
 BUILDING PROVISO: SEPARATE PERMIT IS REQUIRED REVIEWED
 UNDER MASTER.
 NOA 12-0514.04 FIRESTONE - FIRESTONE ULTRA PLY TPO &
 TPO XR SINGLE PLY ROOF SYSTEMS OVER STEEL DECK.
 ++++++++++++++++++++++++++++++++++
 SHOP DRAWING STAMP COVER SHEET LIST THE FOLLOWING
 NOTES:
 1) PAGE 28 MECHANICALLY FASTENED ZONE 1
 2) PAGE 6 FULLY ADHERED INSTALATION FOR ZONE 2
 3) GENERAL LIMITATION # 7 ALLOWS FOR ZONE 3
 INSTALLATION PAGE 8 DEFINES ZONE 3
 4) INSULATION SEE PAGE 12 R-VALUE PAGE 30.
 ++++++++++++++++++++++++++++++++++
  
 NOA 11-1013.05 ALUMINUM SLIDING DOOR- NON-MOTORIZED HIS
 TYPE DOOR NOT SHOWN IN DOOR SCHEDULE PLEASE REMOVE FROM
 PACKAGE.
  
  
  
  
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  