Plan Review Notes
Plan Review Notes For Permit 13071098
Permit Number 13071098
Review Stop B
Sequence Number 2
Notes
Date Text
2013-10-29 10:51:32BUILDING PLAN REVIEW
 PERMIT: 13071098
 ADD: 1865 PALM BEACH LAKES BLDG' "B1"SHELL
 CONT: EMJ KERI NEVEL
 TEL: (561)###-####
 2010 FLORIDA BUILDING CODE W
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
 2012 FBC SUPPLEMENTS ADOPTED APRIL 25/2013.
  
 2010 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 DATE: TUESDAY OCT. 29/2013
 ACTION: DENIED
  
  
 1-4A) COMPLIED.
  
 4B) 2ND REQUEST FOUNDATIONS INDICATES THERE IS A SOILS
 REPORT THAT HAS BEEN COMPLETED, PLEASE SUPPLY REPORT BY
 ECS DATED JUNE 16/ 2012. 2010 FBC-B 1803.2
 INVESTIGATION REQUIED.
  
 4C) 2ND REQUEST, ADDING ANOTE TO THE PLANS DOES NOT
 MEET CODE COMPLIANCE. UNDER THE HEADING TILT-UP
 CONCRETE WALL PANELS, CITY OF WEST PALM BEACH LOCAL
 AMENDMENTS TO THE FLORIDA BUILDING CODE (FBC) 2010
 CHAPTER 1 ADMINISTRATION 110.3.9 OTHER INSPECTION
 SEERVICES, THIS PROJECT BEING TILT WALL WILL QUALIFY
 FOR A RESIDENT INSPECTOR. SUCH INSPECTORS SHALL BE
 ADEQUATELY PRESENT AT TIMES WORK IS UNDERWAY ON THE
 STRUCTURAL ELEMENTS OF THE BUILDING. SUCH INSPECTORS
 SHALL BE A REGISTERED ARCHITECT, OR ENGINEER, OR A
 PERSON LICENSED UNDER CHAPTER 468, PART XII, FLORIDA
 STATUTES. SUCH INSPECTORS SHALL SUBMIT WEEKLY PROGRESS
 REPORTS INCLUDING THE DAILY INSPECTIONS TO THE BUILDING
 OFFICIAL, AND INCLUDING A CODE COMPLIANCE OPINION OF
 THE RESIDENT INSPECTOR.
 PLEASE CONTACT KEN CONRAD THE DIRECTOR OF THE RESIDENT
 INSPECTOR PROGRAM FOR REQUIREMENTS FORMS AND ADDITIONAL
 INFORMATION ON THIS PROGRAM AND REQUIREMENTS :
 KEN CONRAD
 TEL: 561-805-6666
 FAX: 561-805-6676
 E-MAIL: KCONRAD @WPB.ORG
  
 5) BUILDING PROVISO:GC TO SUBMIT SIGNED & SEALED SHOP
 DRAWING, FL 61G1-23.015 (2) THE ARCHITECT IS
 RESPONSIBLE FOR SUPERVISING AND REVIEWING ALL PROJECT
 DATA, REPORTS, SHOP DRAWINGS ETC...BEFORE SUBMITTAL TO
 THE BUILDING DEPARTMENT.
 SHEET S002 RTU HEADING THE NOTE AS FOLLOWS: GC TO
 PROVIDE PRE-ENGINEERED RTU TIE DOWNS OR EQUIVALENT
 ENGINEERED TIE-DOWN SOLUTIONS THAT MEET OR EXCEEDS TTHE
 REQUIRED WIND DESIGN CRITERIA. PLEASE PROVIDE
 ENGINEERING FOR ROOF TOP UNITS PER 2010 FBC-B 1609.8
 ROOF TOP STRUCTURES & EQUIPMENT.
  
 6) 2ND REQUEST, ADDING THE GENERAL NOTE # 13 TO THE
 COVER SHEET DOES NOT RELIEVE THE DESIGNER OF RECORD
 FROM REVIEWING THE PRODUCT APPROVALS BEFORE SUBMITTAL
 TO THE BUILDING DEPARTMENT.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC...
 WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE PRODUCT
 WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
  
 7) PLEASE SUBMIT THE FOLLOWING PRODUCT APPROVALS: 2010
 FBC-B 1609.1.2 PROTECTION OF OPENINGS, 1609.6.4.41
 COMPONENTS & CLADDING
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS, SWING DOORS, ROLL UP DOORS &
 ROOF HATCH .NOT REVIEWED BY DESIGNER OF RECORD
  
 11-0722.10 ROOF HATCH +/- 70 PSF
 PLEASE REVIEW SHEET A-141, TENANT B-12 THIS ROOF HATCH
 IS IN ROOF ZONE # 2 WITH ASSOCIATED PRESSURES OF -76.5
 IN EXCESS OF THE PRODUCT APPROVAL , TENANTS B13, B14 &
 B15 OK.
  
 NOA 11-1013.05 ALUMINUM SLIDING DOOR- NON-MOTORIZED HIS
 TYPE DOOR NOT SHOWN IN DOOR SCHEDULE PLEASE REMOVE FROM
 PACKAGE.
 (B) WINDOWS NOT REVIEWED BY THE DESIGNER OF RECORD
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS, NOT REVIEWED BY DESIGN OF
 RECORD.
 (D) ROOFING PRODUCTS AND ASSEMBLIES NOTE BOTH FOR FULLY
 ADHERRED SYSTEMS AND MECHANICALLY FASTENED SYSTEMS,
 ALSO INCLUDE ROOF TOP INSULATION, & A/C CURBING.
  
 NOA 03-0625 FIRESTONE -EXPIRED, PLEASE REMOVE FROM
 PACKAGE
 NOA 12-0625.02 FIRESTONE NO SUB-SYSTEM IS CIRCLED,
 IDENTIFYING WHICH SYSTEM IS TO BE INSTALLED W/
 ASSOCIATED PRESSURES/ NO ROOFING INSULATION IDENTIFIED
  
 A(3RD) PRODUCT NOA08-0603.19 GAF SINGLE PLY TPO WAS
 SUMITTED NO SUB-SYSTEM INDENTIFIED, NOTE NOA 13-0603.19
 SUBMITTED INSULATION YPE OR SIZE NOT IDENTIFIED.
  
 F) SHUTTERS- NOA 13-0422.14 ALUMINUM /CANVAS AWNINGS +/
 50 PSF.
 3105.4.1
 DESIGN OF THE FRAMING MEMBERS SHALL NOT BE BASED ON
 REMOVAL OR REPOSITIONING OF PARTS, OR THE WHOLE, DURING
 PERIODS OF 75 MPH WIND VELOCITY.
 3105.4.2 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL
 BE BASED ON RATIONAL ANALYSIS, USING THE APPLICABLE
 WIND LOADS OF CHAPTER 16 AS SHOWN BELOW:
  
 3105.4.2.1 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1. MINIMUM WIND SPEED 105 MPH
 2. EXPOSURE CATEGORY B, C OR D AS DEFINED IN CHAPTER
 16.
 3105.4.2.2 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE COVERED STRUCTURE DESIGNED WITH A PERMANENT OR
 NONREMOVABLE FABRIC OR MEMBRANE, SHALL BE BASED ON THE
 FOLLOWING CRITERIA:
 1. MINIMUM WIND SPEED VELOCITY AS REQUIRED IN CHAPTER
 16 USING FIGURE 1609C.
 2. EXPOSURE B, C OR D AS DEFINED IN CHAPTER 16.
 3105.4.3 THE FABRIC PORTIONS OF AWNINGS FABRIC COVERED
 FRAMES SHALL BE SECURELY LACED, TIED OR OTHERWISE
 FASTENED TO THE FRAME; NO RAFTER OR FRONT BAR WILL BE
 PERMITTED IN POCKETS; AND IN NO CASE SHALL A ROLLING
 CURTAIN BE CAUSED TO OPERATE OVER A CANOPY FRAME.
 3105.4.4 THE HORIZONTAL PROJECTION OF CANTILEVERED
 PORTIONS SHALL NOT BE GREATER THAN TWO TIMES THE
 HEIGHT, EXCEPT WHERE THE BUILDING CONSTRUCTION DOES NOT
 PERMIT A PROPER INSTALLATION; IN WHICH CASE, VARIANCE
 MAY BE PERMITTED BY THE BUILDING OFFICIAL, BASED ON
 SPECIAL DESIGN AND CONSTRUCTION.
  
 (G) PRE-ENGINEERED A/C STANDS IF THEY ARE GOING TO BE
 INSTALLED NO APPROVALS SUBMITTED.
  
 8-9) COMPLIED.
  
 10) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  
  
  