| 2013-08-24 11:44:22 | 1801 PALM BEACH LAKES BOULEVARD - BULK MERCHANDISING |
| | RETAIL |
| | PERMIT #13071098 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE ADDRESS IS INDICATED AS 1801 PALM BEACH LAKES |
| | BOULEVARD; HOWEVER, THIS BUILDING ADDRESS ALREADY |
| | EXISTS ON THIS SITE FOR THE OUTLET MALL (BUILDING J1). |
| | |
| | PER SECTION 10.12.1.2 (NFPA 1), PROVIDE BUILDING |
| | ADDRESS VISIBLE FROM THE STREET. NUMBERS SHALL BE |
| | ATTACHED TO THE BUILDING AND BE AT LEAST SIX-INCHES IN |
| | HEIGHT WITH 1-INCH STROKE AND SHALL CONTRAST THE |
| | BACKGROUND. |
| | |
| | PROVIDE DRAWING NOTE INDICATING ALL CONSTRUCTION WORK |
| | SHALL CONFORM TO THE REQUIREMENTS OF NFPA 241. TRASH |
| | AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE SITE |
| | DAILY. SMOKING SHALL BE PROHIBITED EXCEPT IN DESIGNATED |
| | EXTERIOR AREAS. ALL OTHER DEMOLITION OR CONSTRUCTION |
| | AREAS SHALL HAVE "NO SMOKING" SIGNS POSTED. WHERE |
| | SMOKING IS PERMITTED, SAFE RECEPTACLES FOR SMOKING |
| | MATERIALS SHALL BE PROVIDED. |
| | |
| | ENGINEERED FIRE ALARM AND FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. PER FBC SECTION 907.1.1 CONSTRUCTION |
| | DOCUMENTS - "CONSTRUCTION DOCUMENTS FOR FIRE ALARM |
| | SYSTEMS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE, THE FLORIDA FIRE PREVENTION CODE, AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL." FOR ISSUANCE OF A |
| | GENERAL BUILDING PERMIT, SECTION 105.3.1.2(2) OF THE |
| | FLORIDA BUILDING CODE REQUIRES SEALED FIRE PROTECTION |
| | CONSTRUCTION DOCUMENTS FOR THE DESIGN OR ALTERATION OF |
| | 50 OR MORE AUTOMATIC FIRE SPRINKLERS. PER FLORIDA |
| | ADMINISTRATIVE CODE SECTION 61G15-32.004, FIRE |
| | PROTECTION ENGINEERING DOCUMENTS SHALL INCLUDE THE |
| | POINT OF SERVICE FOR THE WATER SUPPLY, A LIST OF |
| | APPLICABLE NFPA STANDARDS APPLICABLE TO THE PROJECT, |
| | CLASSIFICATION OF HAZARD OCCUPANCY FOR EACH ROOM OR |
| | AREA, SUPPRESSION SYSTEM TYPE, DESIGN DENSITIES, WATER |
| | SUPPLY DATA (FIRE PUMP DATA, HYDRANT FLOW TEST DATA) |
| | AND ANY PERFORMANCE BASED INFORMATION SUCH AS |
| | PRE-ENGINEERED SYSTEMS. |
| | |
| | |
| | NOTE: THE MAIN ENTRY IS PERMITTED TO BE EQUIPPED WITH A |
| | KEYED LOCK WITH LOCK/UNLOCK INDICATOR WINDOW AND |
| | SIGNAGE STATING THE DOOR IS TO REMAIN UNLOCKED DURING |
| | BUSINESS HOURS. NO OTHER LOCKING OR LATCHING MECHANISMS |
| | ARE PERMITTED.THUMB-TURN LOCKS TO BE EQUIPPED WITH A |
| | LOCK/UNLOCK INDICATOR. |
| | |